Section 8 - LCD Keypad Programming Questions
8–17
partition boundaries each of these users will contain a master partition value, such that
users with the proper authority level can program only those users that have the same
master partition number.
For example, to prevent authorized users within partition one from changing user codes
assigned to partition two, simply program the users in partition #1 to have a master
partition of one, and the users in partition two to have a master partition of two.
System Attributes
The System Attributes defines the parameters that are common to all zones and partitions
within the control panel.
Expansion Modules
031 EXPAND MODE
NO EXPAND
This question selects which zone expansion module is present in the control panel. Press the
0 key to toggle through the available choices:
NO EXPAND
Zone expander slot empty - Control panel contains 8 hardwired zones
only.
8 ZONE EXP.
Model 7105 zone expander module is present. Total of 16 zones
consisting of the 8 zones on-board and 8 additional hardwired zones
through the expander module.
MUX EXPAND 1
Multiplex expansion module present. Multiplex expansion module
model 7120 is used for the XL-4 and XL-4B and expansion module
model 7126 is used in the XL-5 The system contains 8 hardwired
zones plus up to 64 multiplex points (XL-4 and XL-4B) or 120
multiplex points (XL-5), using a two wire multiplex bus. The
multiplex zones are known as 9 – 72 (XL-4 and XL-4B) or 9 – 128
(XL-5).
The MUX EXPAND 1 option will scan the multiplex bus upon reset
and will find the active points connected to the bus. Using this auto
scan mode, the active devices must be programmed within the
programming sequence to the desired attributes and connected to the
bus and be operational prior to the system reset. NOTE: The reset
occurs during a total power-up or after exiting programming (keypad
or remote).
MUX EXPAND 2
Multiplex expansion module present. Multiplex expansion module
model 7120 is used for the XL-4 and XL-4B and expansion module
model 7126 is used in the XL-5 The system contains 8 hardwired
zones plus up to 64 multiplex points (XL-4 and XL-4B) or 120
multiplex points (XL-5), using a two wire multiplex bus. The
multiplex zones are known as 9 – 72 (XL-4 and XL-4B) or 9 – 128
(XL-5).
Under MUX EXPANDER 2 the valid zones connected to the multiplex
bus are determined by the zone definitions. An active multiplex zone
will be defined as any zone (9 – 72 or 9 - 128) which contains a zone
definition with at least one condition that can cause an alarm/trouble.
See questions 160 - 163. In this mode an inactive zone would be a
zone that would contain the alarm/trouble on open/short questions all
programmed as NO.
Содержание XL-4
Страница 1: ...N9145V2 10 98 6HFXULW 6 VWHP 3URJUDPPLQJ XLGH 9HUVLRQ...
Страница 6: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 1 2...
Страница 12: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 2 6...
Страница 14: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 3 2...
Страница 18: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 5 2...
Страница 88: ...XL 4 XL 4B and XL 5 LCD Keypad Programming Manual Version 4 8 66...
Страница 100: ...1 9 Al N9145V2 10 98 Subsidiary of Pittway Corp 149 Eileen Way Syosset New York 11791 Copyright 1998 PITTWAY CORPORATION...