APPLICATION EXAMPLE 3:
In this example it is explained what occurs when it is selected in curve type parameter
“DEFINITE TIME”. In this case, 50/51 function works as 50 function.
Starting from the following information
Line details:
•
Transformation ratio of CT =100/1
•
Primary current: Ip=100 A
50/51 function settings
•
Curve type: Definite time
•
Tap 1xIn
•
Time delay: 5 s
50 function settings
•
Tap: 15xIn
•
Time delay: 1 s
Figure 5. Function 50/51 (as 50) and function 50.