4.12. Trip block for switch disconnector
Some transformation centers use a combination of switchgear and fuses for cutting out.
Switchgears have a limited opening current. As a result, the fuses are responsible for cutting out
the circuit for high current short circuits, as the switchgear would be destroyed if opened in this
situation. In order to deal with these situations, tripping is blocked when the phase current
exceeds a pre-set value.
Group
Description
Minimum
Maximum
Step
Unit
Default
Trip block protection for switchdisconnector
Blocking
-
-
Yes/No
-
Yes
Blocking limit
1.50
20.00
0.01
I nominal
7.00
Содержание SIL-D00
Страница 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Страница 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Страница 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Страница 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Страница 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Страница 49: ...www fanox com Rev 06 49 226...
Страница 50: ...www fanox com Rev 06 50 226...
Страница 51: ...www fanox com Rev 06 51 226...
Страница 52: ...www fanox com Rev 06 52 226...
Страница 111: ...www fanox com Rev 06 111 226 I C 3 7 0 00 A C I N 4 7 0 00 A C V R 5 7 0 00 V D Ang 6 7 0 00 deg C IMax 7 7 0 00 A...
Страница 200: ...www fanox com Rev 06 200 226...
Страница 224: ...www fanox com Rev 06 224 226 14 9 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 225: ...www fanox com Rev 06 225 226 NOTES...
Страница 226: ...www fanox com Rev 06 226 226...