The actuation time is accurate to ±5%, o ±30ms, whichever is higher, of the theoretical actuation
time.
If function 67N is configured with forward or reverse directionality, a directionality supervision
time of 20ms in the actuation will be introduced.
The curves that are used are IEC 60255-151 and IEEE, which are described in the
corresponding section.
The following figures show a graphic representation of the directional actuation zone, adjusted
with an operating angle of 90° and a half-cone angle of 60°:
Forward