Rev.06
148/226
▲▼
Time Delay
0.02 s
C
Sett(1) T. Block
C
↑
SETTINGS
GEN
↓
COM
"
OK
Function Enable
NO
C
Sett(1) T. Block
▲▼
Current Tap
7.00 xIn
Press the “◄” key to access the general settings from the "SETTINGS" screen.
The general setting "Equipment name" can be viewed and modified from the HMI and from SICom software.
The frequency can be 50 or 60 Hz.
Serial number is a read only setting.
The value of the "CT Phase ratio” and “CT Neutral ratio” general settings is the result given by dividing the number of turns on the primary winding by the
number on the secondary winding. For example: With TI 500/5, the setting would be 100 in standard models.
Содержание SIL-D00
Страница 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Страница 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Страница 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Страница 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Страница 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Страница 49: ...www fanox com Rev 06 49 226...
Страница 50: ...www fanox com Rev 06 50 226...
Страница 51: ...www fanox com Rev 06 51 226...
Страница 52: ...www fanox com Rev 06 52 226...
Страница 111: ...www fanox com Rev 06 111 226 I C 3 7 0 00 A C I N 4 7 0 00 A C V R 5 7 0 00 V D Ang 6 7 0 00 deg C IMax 7 7 0 00 A...
Страница 200: ...www fanox com Rev 06 200 226...
Страница 224: ...www fanox com Rev 06 224 226 14 9 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 225: ...www fanox com Rev 06 225 226 NOTES...
Страница 226: ...www fanox com Rev 06 226 226...