Rev.06
33/226
4.6. Function 59N. Definite-time neutral overvoltage
This protection function is adjusted using four parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
59N
Definite-time neutral overvoltage
Permission
-
-
Yes/No
-
No
Pickup
2.0
65.0
0.1
V
40.0
Time Delay
0,02
300,00
0.01
s
10.00
Reset time
0,02
300,00
0.01
s
0,20
The operating time is completely independent of the measured neutral voltage, such that should
the neutral voltage exceed the set value during the same amount of time or more than the set
one during operation time, the protection function acts (trips) and there it is not restored until the
measured value of the neutral voltage drops below the voltage set point during adjusting reset
time.
The function pick up occurs at 100% of the adjusted input and the dropout at 95%. The reset
type is temporized and reset time is adjusted with reset time parameter.
The accuracy of the Time delay is equal to the preset time ±30 ms or ±0.5%
Содержание SIL-D00
Страница 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Страница 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Страница 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Страница 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Страница 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Страница 49: ...www fanox com Rev 06 49 226...
Страница 50: ...www fanox com Rev 06 50 226...
Страница 51: ...www fanox com Rev 06 51 226...
Страница 52: ...www fanox com Rev 06 52 226...
Страница 111: ...www fanox com Rev 06 111 226 I C 3 7 0 00 A C I N 4 7 0 00 A C V R 5 7 0 00 V D Ang 6 7 0 00 deg C IMax 7 7 0 00 A...
Страница 200: ...www fanox com Rev 06 200 226...
Страница 224: ...www fanox com Rev 06 224 226 14 9 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 225: ...www fanox com Rev 06 225 226 NOTES...
Страница 226: ...www fanox com Rev 06 226 226...