SIA-D_
Rev. 07
34 / 117
ISO 9001:2008
Group
Description
Minimum
Maximum
Step
Unit
Default
Tripping bus
Application
-
-
(3*)
-
No activado
50P tripping bus
permission
-
-
Yes/No
-
Yes
51P tripping bus
permission
-
-
Yes/No
-
Yes
50N tripping bus
permission
-
-
Yes/No
-
Yes
51N tripping bus
permission
-
-
Yes/No
-
Yes
67N1 tripping
bus permission
-
-
Yes/No
-
Yes
67N2 tripping
bus permission
-
-
Yes/No
-
Yes
Phase blocking
time
0
300,0
0,01
s
0
Neutral blocking
time
0
300,0
0,01
s
0
Phase signalling
time
0
300,0
0,01
s
0
Neutral
signalling time
0
300,0
0,01
s
0
General
Equipment's
identifier
- - - -
“www.fanox.com”
(1*)
TI phase relation
1
2000
1
-
100
TI neutral
relation
1 2000 1 -
100
Frequency - - 60/50
Hz
50
(2*)
Language 0 3 1 -
ENGLISH
TT neutral
relation
1 2000 1 -
100
(1*) The equipment identifier setting can only be set through communications.
(2*) The frequency setting is read only. The equipment frequency is selected from the list of
models.
(3*) Not activated, Feeder, Supply, Feeder and Supply
The rest of the settings can be changed either from the HMI or through communications.
Содержание SIA D
Страница 1: ...www fanox com SIA D_Rev 07 1 117 ISO 9001 2008 USER MANUAL SIA D Overcurrent relay...
Страница 36: ...www fanox com SIA D_Rev 07 36 117 ISO 9001 2008...
Страница 37: ...www fanox com SIA D_Rev 07 37 117 ISO 9001 2008...
Страница 38: ...www fanox com SIA D_Rev 07 38 117 ISO 9001 2008...
Страница 58: ...www fanox com SIA D_Rev 07 58 117 ISO 9001 2008...
Страница 60: ...www fanox com SIA D_Rev 07 60 117 ISO 9001 2008...
Страница 116: ...www fanox com SIA D_Rev 07 116 117 ISO 9001 2008 10 8 NOTES...