Settings associated to tripping bus are the following:
Function
Description
Minimum
Maximum
Pass
Unit
Default
TRIPPING BUS
Tripping Bus
Application -
-
(1*)
-
Not
activated
50P Tripping bus permission
-
-
Yes/no
-
Yes
51P Tripping bus permission
-
-
Yes/no
-
Yes
50N Tripping bus permission
-
-
Yes/no
-
Yes
51N Tripping bus permission
-
-
Yes/no
-
Yes
67N1 Tripping bus permission
-
-
Yes/no
-
Yes
67N2 Tripping bus permission
-
-
Yes/no
-
Yes
Phase blocking time
0
300
0,01
s
0
Neutral blocking time
0
300
0,01
s
0
Phase blocking signalling time
0
300
0,01
s
0
Neutral blocking signalling time
0
300
0,01
s
0
(1*) Not activated, Feeder, Supply, Feeder and Supply
States associated to tripping bus are the following:
Group
State
Cause
Associated measurement
TRIPPING
BUS
50P block
Activation /Deactivation
-
51P block
Activation /Deactivation
-
50N block
Activation /Deactivation
-
51N block
Activation /Deactivation
-
67N1 block
Activation /Deactivation
-
67N2 block
Activation /Deactivation
-
50P block signalling
Activation /Deactivation
-
51P block signalling
Activation /Deactivation
-
50N block signalling
Activation /Deactivation
-
51N block signalling
Activation /Deactivation
-
67N1 block signalling
Activation /Deactivation
-
67N2 block signalling
Activation /Deactivation
-
Содержание SIA D
Страница 1: ...www fanox com SIA D_Rev 07 1 117 ISO 9001 2008 USER MANUAL SIA D Overcurrent relay...
Страница 36: ...www fanox com SIA D_Rev 07 36 117 ISO 9001 2008...
Страница 37: ...www fanox com SIA D_Rev 07 37 117 ISO 9001 2008...
Страница 38: ...www fanox com SIA D_Rev 07 38 117 ISO 9001 2008...
Страница 58: ...www fanox com SIA D_Rev 07 58 117 ISO 9001 2008...
Страница 60: ...www fanox com SIA D_Rev 07 60 117 ISO 9001 2008...
Страница 116: ...www fanox com SIA D_Rev 07 116 117 ISO 9001 2008 10 8 NOTES...