www.fanox.com
SIA-D_
Rev. 07
27 / 117
ISO 9001:2008
•
Residual voltage that is higher than the setting
•
Residual current that is higher than the setting
•
The phase difference of the residual current and the residual voltage is at a level where the
residual current is within the working range.
The function settings are shown below:
Group
Description
Minimum
Maximum
Step
Unit
Default
67N
Neutral directional overcurrent
Permission -
-
Yes/No
-
No
Tap
0,10 30,00 0,01 I
nominal 5,00
Operating
time 0,02 300,0 0,01
s
0,02
Directionality -
-
Yes/No
- No
Residual voltage
4,00
110,00
0,1
V
5
Operating angle
0
359
1
º
90
Half-cone angle
0
170
1
º
90
The residual current's activation level is 100% and the reset level is 95%. The residual voltage's
activation level is 100% and the reset level is 95%. The reset is instantaneous.
The accuracy of the operation time is equal to the preset time plus a maximum of 30 ms.
The operation area of the directional adjusted to an operation angle of 90º and a semi-cone angle of
60º is graphically shown below.
Содержание SIA D
Страница 1: ...www fanox com SIA D_Rev 07 1 117 ISO 9001 2008 USER MANUAL SIA D Overcurrent relay...
Страница 36: ...www fanox com SIA D_Rev 07 36 117 ISO 9001 2008...
Страница 37: ...www fanox com SIA D_Rev 07 37 117 ISO 9001 2008...
Страница 38: ...www fanox com SIA D_Rev 07 38 117 ISO 9001 2008...
Страница 58: ...www fanox com SIA D_Rev 07 58 117 ISO 9001 2008...
Страница 60: ...www fanox com SIA D_Rev 07 60 117 ISO 9001 2008...
Страница 116: ...www fanox com SIA D_Rev 07 116 117 ISO 9001 2008 10 8 NOTES...