2.7 Connection
2.7.1 Input Connection
The user connects the three-phase wire and the ground wire to the power supply input terminal as shown in
Figure 2-6. For the size of the wire diameter, please refer to "Table 6-1 Recommended Wire Diameter for Cables".
Figure 2-6 Power supply Input Connection
----------------------------------------------------------------------------------------------------------------------------
1. To protect the operator, the wire connected to the GND terminal must be connected to
the earth. Under no circumstances shall this DC Power Supply be operated without an
adequate ground connection.
2. Installation of the power cord must be done by a professional and compliant with local
electrical codes.
----------------------------------------------------------------------------------------------------------------------------
2.7.2 Input Connection for Multiple Power Supplies
If multiple 5kW or 10kW models are connected to the grid, it is recommended to distribute the access points in a
balanced manner as shown in the figure below. When the 15kW model is connected to the three-phase power
grid, there is no need to consider the imbalance of the power grid.
Figure 2-7 Input Connection of multiple 5kW Models
Figure 2-8 Input Connection of multiple 10kW Models