![fafnir TORRIX XTS Series Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/fafnir/torrix-xts-series/torrix-xts-series_technical-documentation-manual_3185396017.webp)
Electrical connection
Page 14/
47
5.2
Maximum Length of the Connection Cable
The permissible total resistance of the cable and the load (see chapter
) must not be
exceeded.
The cable (length and cross-section) must be chosen so that the supply voltage
will not fall below the sensor-specific minimum voltage (12 V) in the case of
the highest current consumption (21.5 mA).
Always make sure that the permissible external capacitance (C
o
) and inductance
(L
o
) of the associated apparatus are not exceeded (refer to the electrical data in
the EU-Type Examination Certificate of the apparatus) if the intrinsically safe
level sensor is used in a potentially explosive atmosphere.
The following table shows the resistances of different copper wire cross-sections:
Cable cross-section Q [mm²]
Cable resistance R
Q
per m copper cable [
Ω/
m]
0.5
0.0356
1.0
0.0178
1.5
0.0119
Example: A 1000 m long, cross-
section 0.5 mm² copper cable with outgoing and return
lines (2
-core) has a cable resistance of approximately
70
Ω
.
The maximum cable length is calculated as follows:
L = (((U – U
min
) / I
max
) – R
B
) / R
Q
L = Cable length [m]
U = Supply voltage [V] (with negative tolerance value -
5
%)
U
min
=
Minimum supply voltage [V] = 12 V
DC
I
max
= Maximum power
consumption [A] = 0,0215
A
R
B
= Load
R
Q
= Cable resistance per m cable [
Ω/
m] for cable cross-
section Q [mm²]
Example:
Supply voltage = 24 V
DC
(± 5
%), supply voltage U = 22.8 V
DC
(24 V
DC
-
5
%),
minimum supply voltage U
min
= 12 V
DC
, current consumption I
max
= 0.0215 A,
load R
B
= 100
Ω,
cable cross-
section Q = 0.5 mm², cable resistance R
Q
= 0.0356 Ω/
m
A copper cable with outgoing and return lines (2
-
core) could theoretically be up to 5650 m
long with the parameters of this example.
Содержание TORRIX XTS Series
Страница 51: ...Blank Page...