Page 11/
47
Electrical connection
5
Electrical connection
5.1
Connection Diagrams
5.1.1
Wiring diagram TORRIX XTS
The level sensor without Ex approval is installed according to the following wiring diagram:
Figure
7
: Wiring diagram TORRIX XTS
Maximum power supply U
max
= 50 V
DC
Minimum supply voltage U
min
= 12 V
DC
Permissible total resistance (incl. line resistances and load)
Σ
R = (U - U
min
) / 0.0215 A
Example:
Standard supply
voltage of 24 V
DC
with a negative tolerance value of -
5
%
Σ
R = (24 V
DC
x 0.95
–
12 V
DC
) / 0.0215 A = 502 Ω
The permissible total resistance is about 500
Ω
.
+
+
_
Y
I
R1
R2
R3
U
TORRIX
Spannungsquelle
Leitungswiderstände
Bürde
U
= 30 V
max
U
= 8 V
min
Line resistances
Power supply
Power supply
U
max
= 50 V
DC
Load
U
min
= 12 V
DC
Line resistances
TORRIX XTS
Содержание TORRIX XTS Series
Страница 51: ...Blank Page...