Page 70
8. Setting of parameters
Configuration external modules
Range
Default
A71 Configuration stirring unit monitoring
0 ..
0
15
look also section 9.22
0: deactivated
5: Clear bands (after deletin of the band , the
g
s
number of agitators must be readjusted)
Agitator monitoring module ESVAW-002-A
with two agitator switch-on-relays that are integrated in the module
6: one agitator
7: two agitators (if not used with [A14] other functions are selectable)
Agitator monitoring module ESVAW-003-A
with one agitator switch-on-relay that is integrated in the module
12: One agitator 3-phases 400 V
13: Two agitators 3-phases 400V
(over second module. Note addressing)
14: One agitator 2-phases 400V
15: Two agitators 2- phases 400V
(over second module. Note addressing)
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Agitator monitoring without a separate module
If
monitoring is made via inductive
agitator
agitator
sensor (max. 2 channels)
8: one agitator
9: two agitators
If
monitoring is made via switch contact
agitator
of the Gala-Kool Pro
10: one agitator
11: two agitators
A73
ctivation GSM alarm module
A
monitoring
0 ..
0
4
1: activated, do not forward alarm messages
2: activated, forward Tank Monitor alarm messages
3: activated, forward General Alarm messages
4: activated, forward all alarm messages
A74 Activation of external IO-Module
0 .. 1 0
0: deactivated
1 activated
:
A75
ctivation power pack
A
0 ..
0
2
see section 9.21
0: deactivated
1: battery operation with voltage monitoring
)
2: power supply operation (error message for power failure are deactivated
8.10 Level “Configuration” (A parameters)