CHANNEL LIST DAAB AUTOMATIC CONTROL UNIT EP104 4.08
41
Channel list edition 1 for EP104 version 4.08
Programmable output 6
No.
Name
Range
Factory Setting
o600
Function of output 1
0 - 4
0
0
Disabled
1
Position indication/Movement/Warning. Signal as configured in o610 – o622
2
Presence detection/Direction sensing. Signal as configured in o691
3
Lock
4
Alarm output Signal as configured in o630 – o642
o610
Open position
0 - 1
0
0
Disabled
1
Constant signal
o611
Mid position
0 - 1
0
0
Disabled
1
Constant signal
o612
Closed position
0 - 1
0
0
Disabled
1
Constant signal
o613
Movement
0 - 4
4
0
Disabled
1
Constant signal in the opening movement
2
Constant signal in the closing movement
3
Constant signal in the opening and closing movement
4
No signal during movement, used in combination with o610, o611 and o612.
o614
Delayed switch-off Switch off after the specified time For
example to switch off lighting a specified time after closing
0.00-9.59 minutes
0.00
o620
Warning time before start
0.00-9.59 minutes
0.00
o621
Warning function in combination with o620
1 - 4
2
1
Constant signal before automatic closing
2
Constant signal before park and automatic closing
3
Constant signal before close signal, park and automatic closing
4
Constant signal before all signals
o622
Function during warning time
1 - 2
1
1
Output signal disabled during warning in other output
2
Output signal as configured in o610-o613