CHANNEL LIST DAAB AUTOMATIC CONTROL UNIT EP104 4.08
38
Channel list edition 1 for EP104 version 4.08
Programmable output 5
No.
Name
Range
Factory Setting
o500
Function of output 1
0 - 4
0
0
Disabled
1
Position indication/Movement/Warning. Signal as configured in o510 – o522
2
Presence detection/Direction sensing. Signal as configured in o591
3
Lock
4
Alarm output Signal as configured in o530 – o542
o510
Open position
0 - 1
0
0
Disabled
1
Constant signal
o511
Mid position
0 - 1
0
0
Disabled
1
Constant signal
o512
Closed position
0 - 1
0
0
Disabled
1
Constant signal
o513
Movement
0 - 4
4
0
Disabled
1
Constant signal in the opening movement
2
Constant signal in the closing movement
3
Constant signal in the opening and closing movement
4
No signal during movement, used in combination with o510, o511 and o512.
o514
Delayed switch-off Switch off after the specified time For
example to switch off lighting a specified time after closing
0.00-9.59 minutes
0.00
o520
Warning time before start
0.00-9.59 minutes
0.00
o521
Warning function in combination with o520
1 - 4
2
1
Constant signal before automatic closing
2
Constant signal before park and automatic closing
3
Constant signal before close signal, park and automatic closing
4
Constant signal before all signals
o522
Function during warning time
1 - 2
1
1
Output signal disabled during warning in other output
2
Output signal as configured in o510-o513