CHANNEL LIST DAAB AUTOMATIC CONTROL UNIT EP104 4.08
29
Channel list edition 1 for EP104 version 4.08
Programmable output 2
No.
Name
Range
Factory
Setting
o200
Function of output 2
0 - 4
1
0
Disabled
1
Position indication/Movement/Warning. Signal as configured in o210 – o222
2
Presence detection/Direction sensing. Signal as configured in o291
3
Lock
4
Alarm output Signal as configured in o230 – o242
o210
Open position
0 - 1
0
0
Disabled
1
Constant signal
o211
Mid position
0 - 1
0
0
Disabled
1
Constant signal
o212
Closed position
0 - 1
1
0
Disabled
1
Constant signal
o213
Movement
0 - 4
4
0
Disabled
1
Constant signal in the opening movement
2
Constant signal in the closing movement
3
Constant signal in the opening and closing movement
4
No signal during movement, used in combination with o210, o211 and o212.
o214
Delayed switch-off Switch off after the specified time
For example to switch off lighting a specified time
after closing
0.00-9.59 minutes
0.00
o220
Warning time before start
0.00-9.59 minutes
0.00
o221
Warning function in combination with o220
1 - 4
2
1
Constant signal before automatic closing
2
Constant signal before park and automatic closing
3
Constant signal before close signal, park and automatic closing
4
Constant signal before all signals
o222
Function during warning time
1 - 2
1
1
Output signal disabled during warning in other output
2
Output signal as configured in o210-o213