CHANNEL LIST DAAB AUTOMATIC CONTROL UNIT EP104 4.08
24
Channel list edition 1 for EP104 version 4.08
•
Limit switch, L-channels
No.
Name
Range
Factory
Setting
L001
Choice of limit switch type for motor 1
0-3
0
0
Disabled
1
Encoder
2
Limit switch
3
Time
4
Hold-to-run without limit switches. NOTE! Only one half at a time can be run. C033 must be set to 5.
L002
Choice of limit switch type for motor 2
0-3
0
0
Disabled
1
Encoder
2
Limit switch
3
Time
4
Hold-to-run without limit switches. NOTE! Only one half at a time can be run. C033 must be set to 5.
L110*
Placement of motor 1, viewed from the motor side
0-2
1
0
Disabled
1
Left
2
Right
L111*
Position angle readout, motor 1
000-360 degrees
L112*
Open position angle, motor 1
145-330 degrees
260
L113*
Closed position angle, motor 1
015-180 degrees
90
L116*
Angle for limited opening, motor 1.
0-200 degrees
45
L117*
Angle for the disconnection of safety edges, load
guard and photocells from the end of the closing
movement, motor 1 in combination with C436, C341
and C448
0-30 degrees
0
L118*
Angle for the disconnection of vehicle loops from the
end of the closing movement, motor 1 in combination
with d141 or d241.
0-45 degrees
0
* = Only when L001 are set to 1.