CHANNEL LIST DAAB AUTOMATIC CONTROL UNIT EP104 4.08
33
Channel list edition 1 for EP104 version 4.08
No.
Name
Range
Factory Setting
o330*
Alarm delay. Alarms in channels o331 - o342 must be active this
time to give an output signal.
0.00-9.59 minutes
0.00
o331*
Alarm for faulty safety edge.
0 - 1
0
0
Disabled
1
Constant signal
o332*
Alarm for critical error message in display
0 - 1
0
0
Disabled
1
Constant signal
o333*
Alarm if stop circuit interrupted
0 - 1
0
0
Disabled
1
Constant signal
o334*
Alarm if door open
0 - 1
0
0
Disabled
1
Constant signal
o335*
Alarm if door is in mid position
0 - 1
0
0
Disabled
1
Constant signal
o336*
Alarm if door is in closed position
0 - 1
0
0
Disabled
1
Constant signal
o337*
Alarm if vehicle loop 1 is activated
0 - 1
0
0
Disabled
1
Constant signal
o338*
Alarm if vehicle loop 2 is activated
0 - 1
0
0
Disabled
1
Constant signal
o339*
Alarm if photocell interrupted
0 - 1
0
0
Disabled
1
Constant signal
o342*
Alarm for uncritical error message in display
0 - 1
0
0
Disabled
1
Constant signal
o383
Selection of contact function for output
1 - 2
1
1
Normally open, NO
2
Normally closed, NC
* = Only when o300 is set to 4.