14.2 INPUTS CONFIGURATION
Inputs refers to managing connection with safety devices in closure
and opening and opening actuation devices, safety devices and
other types.
DISABLED input
the input is NOT considered in this mode.
FUNCTION ALWAYS OPEN / AUTOMATIC input
FUNCTION ALWAYS OPEN / AUTOMATIC input
-
this type of input may only be activated on I1, I2, I3 and I4 inputs
as NO or NC contact.
-
With contact active this input overrides an OPEN operating mode.
-
With contact not active this input overrides an AUTOMATIC
operating mode.
-
in an input configured in this mode with SDK EVO and LKEVO, the
functions can be modified, except ALWAYS OPEN / AUTOMATIC.
EXTERNAL OPEN input
-
manages 3 types of input :
1. NO or NC CONTACT (can be selected for I1, I2, I3 and I4 inputs
and E terminal)
2. IN CURRENT (can be selected only for E- and E+ terminals)
3. IN FREQUENCY (can be selected only for E terminal)
-
With active contact of an input configured in this way the leaves
must open and remain in the open status for as long as the input
is active.
-
With inactive contact the pause time elapses and the leaves
close again.
-
the ENERGY SAVING mode can be activated on this input.
-
the TOTAL or PARTIAL function can be selected on this input.
-
this input is NOT considered in NIGHT-TIME or EXIT ONLY modes.
-
activation of this input lights up the OPEN green LED on the
board.
EXIT ONLY / TWO-DIRECTIONAL FUNCTION input
EXIT ONLY / TWO-DIRECTIONAL FUNCTION input
-
this type of input can only be activated on I1, I2, I3 and I4 inputs
as NO or NC contact.
-
With contact active this input overrides an EXIT ONLY operating
mode.
-
With contact not active this input overrides a TWO-DIRECTIONAL
operating mode.
-
in an input configured in this way with SDK EVO and LKEVO,
the functions can be modified, except EXIT ONLY / TWO-DIREC-
TIONAL.
AUTOMATIC OPEN input
-
this type of input can only be activated on I1, I2, I3 and I4 termi-
nals as NO or NC contact.
-
With active contact of an input configured in this way the leaves
must open and remain in the open status for as long as the input
is active.
-
With inactive contact the pause time elapses and the leaves
close again.
-
the ENERGY SAVING mode CANNOT be activated on this input.
-
the TOTAL or PARTIAL function can be selected on this input.
-
this input is NOT considered in NIGHT-TIME mode
-
activation of this input lights up the OPEN green LED on the
board.
SEMI-AUTOMATIC OPEN input
-
this type of input can only be activated on I1, I2, I3 and I4 termi-
nals as NO or NC contact.
-
With active contact of an input configured in this way the leaves
must open and remain in the open status.
-
the ENERGY SAVING mode CANNOT be activated on this input.
-
the TOTAL or PARTIAL function can be selected on this input.
-
this input is NOT considered in NIGHT-TIME mode
-
activation of this input lights up the OPEN green LED on the
board.
PHARMACY OPEN input
-
this type of input may only be activated on I1, I2, I3 and I4 inputs
as NO or NC contact.
-
With active contact of an input configured in this way operation
is as follows.
1. In normal operation it is AUTOMATIC OPEN function
2. In NIGHT-TIME function the leaves open in the percentage selected
and after the pause time the leaves close again.
-
activation of this input lights up the OPEN green LED on the
board.
KEY input
-
this type of input can only be activated on I1, I2, I3 and I4 termi-
nals as NO or NC contact.
-
in NIGHT-TIME mode the input is active and has the same function
as AUTOMATIC OPEN.
-
With active contact of an input configured in this way during
NIGHT-TIME function the leaves must open and remain in open
status for as long as the input is active. Upon deactivation the
night-time pause time elapses and the leaves close again.
-
With active contact of an input configured in this way during
normal operation the leaves must open and remain in open status
for as long as the input is active. Upon deactivation the pause
time elapses and the leaves close again.
-
the ENERGY SAVING mode CANNOT be activated on this input.
-
activation of this input lights up the OPEN green LED on the
board.
CLOSURE SAFETY input
-
this type of input can only be activated on I1, I2, I3, I4, S1, S2, S3
and S4 inputs as NO or NC contact.
-
with activation of an input configured in this mode we have the
following functions:
1. during a closing motion the leaves are inverted.
2. with the leaves open closure is prevented
3. the time selected is reapplied if in a pause status
-
if selected on the input, a TEST procedure is run before a closing
motion.
-
With non active contact of the input immediately closes the
leaves again if the ENERGY SAVING function is active, otherwise
the leaves close again after total or partial opening.
-
activation of this input lights up the SIC_CL red LED on the board.
OPENING SAFETY input
-
this type of input can only be activated on I1, I2, I3, I4, S1, S2, S3
and S4 terminals as NO or NC contact.
-
On the escape route doors the safeties on opening are considered
only beyond the PO % (partial opening) set. Any activations be-
fore this point ARE NOT taken into consideration. Once the PO %
has been exceeded, different behaviours can be had depending
on what has been programmed:
1. with OPENING SAFETY in STOP the motion is stopped (status
11) and this status remains until the safeties on opening are not
disengaged.
2. with OPENING SAFETY in LOW ENERGY the motion proceeds slowly
until fully opened.
-
during an EMERGENCY in OPENING motion, activation of an input
thus configured, with the leaves above the PO %, the motion
proceeds slowly until fully opened.
-
during an EMERGENCY in OPENING motion in NIGHT-TIME func-
tion, activation of an input thus configured, with the leaves above
the PO %, the motion proceeds slowly until fully opened.
-
if, on the input thus configured, a TEST procedure is run before
an opening motion.
-
In NIGHT-TIME function activation of an input configured in this
mode during opening stops the motion. If this operation is not
completed due to active safeties in opening, it will wait until it
can be completed, but if this cannot happen because the night-
time pause time set is exceeded, the leaves return to the closed
position.
-
activation of this input lights up the SIC_OP red LED on the board.