BASIC programming fw version 1.6 or higher
BASIC Function
Default
dF
dF
DEFAULT configuration
It displays whether the board is configured to factory set-
tings (default).
Y
Y
= the board is configured in default
no
no
= at least one value has been modified with respect
to default
If you wish to reload all default settings, set
Y
Y
.
Y
Y
Ln
Ln
LEAF NUMBER
1
1
= 1 leaf
2
2
= 2 leaves
1
1
If the function is modified, SETUP must be performed.
PO
PO
PARTIAL OPEN
Set the opening percentage in Partial operating mode
no
no
= 100% opening
Adjustable from 20% to 95% (MAX) of complete opening
Step = 5%
The minimum width prescribed by the cur-
rent legislation on escape routes must be
respected when adjusting this percentage.
no
no
PA
PA
PAUSE TIME
This allows you to adjust the pause time of the fully open door.
Adjustable from
0
0
to
30
30
s.
Step = 1 s
02
02
The pause time is only active in automatic operation mode.
ES
ES
Energy Saving
no
no
= not enabled
Y
Y
= enabled
no
no
Pn
Pn
NIGHT PAUSE TIME
In night-time mode, if opening is done with the Key com-
mand, the door remains open for the time set with this
function.
Adjustable from
0
0
s to
4
4
minutes (MAX).
from
0
0
to
58
58
s, step = 2 s; time displayed in seconds.
from
58
58
s to
4.0
4.0
minutes, step = 10 s; time displayed in
minutes.tens of seconds: e.g.
1.2
1.2
= 1 minute and 20 seconds.
10
10
CS
CS
CLOSING SPEED
Adjustable from
1
1
(minimum) to
10
10
(MAX).
03
03
OS
OS
OPENING SPEED
Adjustable from
1
1
(minimum) to
10
10
(MAX).
10
10
CF
CF
CLOSING FORCE
Adjustable from
1
1
(minimum) to
10
10
(MAX).
03
03
tF
tF
PUSH TIME on OBSTACLE
Adjustable from
0.1
0.1
s to
3.0
3.0
s.
Step = 0.1 s
1.0
1.0
BASIC Function
Default
Id
Id
INTERNAL DETECTOR INPUT
no
no
= internal detector not enabled
Y
Y
= internal detector in current
Y
Y
(
*
)
Ed
Ed
EXTERNAL DETECTOR INPUT
no
no
= external detector not enabled
1
1
= external detector with contact in frequency
2
2
= external detector in current
3
3
= internal detector in current
4
4
= external detector with N.O. contact
5
5
= external detector with NC contact
4
4
(
*
)
E1
E1
OPEN EMERGENCY CONFIGURATION
no
no
= not enabled
nO
nO
= input with NO contact
nC
nC
= input with NC contact
nO
nO
(
*
)
St
St
EXIT PROGRAMMING
It lets you exit programming, and decide whether to save or
not the modifications made.
Y
Y
= save (only if there are NO configuration errors)
no
no
= do not save
Press F to confirm. After exit, the display shows automation
status:
00
00
CLOSED
01
01
OPENING
02
02
OPEN
03
03
In
PAUSE
04
04
in NIGHT-TIME PAUSE
05
05
CLOSING
06
06
OPEN in EMERGENCY
07
07
in MANUAL mode
08
08
in NIGHT-TIME mode
09
09
OPENING with AUX Motor
10
10
System TEST in progress
11
11
STANDBY
12
12
Safety TEST in progress
13
13
OPEN in ERROR
LO-L2
LO-L2
PHASES LO, L1, L2 SET-UP IN PROGRESS
YY
12
ADVANCED programming fw version 1.6 or higher
ADVANCED Function
Default
P1
P1
SAFETY INPUT CONFIGURATION S1
no
no
= no device
Co
Co
= safety on closure with NO contact
Cc
Cc
= safety on closure with NC contact
Oo
Oo
= safety on opening with NO contact
Oc
Oc
= safety on opening with NC contact
no
no
(
*
)
1F
1F
SAFETY INPUT TEST S1
Not displayed if
PI
PI
=
no
no
YY
= test enabled
no
no
= test not enabled
Y
Y
Содержание A1400 AIR RD
Страница 1: ...A1400 AIR RDT EN16005 2012...
Страница 112: ...A1400 AIR RDT 112 53211904 Rev C...
Страница 116: ...A1400 AIR RDT 116 53211904 Rev C...
Страница 117: ...Translation of the original instructions ENGLISH...