9

ENGLISH

ENGLISH

Vp =  Free transit space
Lt = Head profile length
B = Securing distance of front carriages on sliding leaf.
B1 = Securing distance of rear carriages on sliding leaf.
C = Drive unit positioning dimension
I = Distance: motor unit / transmission pulley
D = Length of top transmission belt
D1 = Lenght of bottom transmission belt
F = Distance between centre of head profile and

centre of  telescopic carriage

940 SMT4/SMTA4 Double-leaf

Fig. 6

SMT transmission unit

Buffer batteries unit

SM Control board unit

Motor/transformer unit

Lt = Vp x 1,5 + 100

Vp

Lt

B

B1

C

I

  D

      D1           F

1400

2200

170

200

1025

900    3745     3885       427

1500

2350

195

225

1075

950    3945

   

 4085       452

1600

2500

220

250

1125

1000    4145

   

 4285       477

1700

2650

245

275

1175

1050    4345     4485       502

1800

2800

270

300

1225

1100    4545     4685       527

1900

2950

295

325

1275

1150    4745     4885       552

2000

3100

320

350

1325

1200    4945     5085       577

2100

3250

345

375

1375

1250    5145     5285       602

2200

3400

370

400

1425

1300    5345     5485       627

2300

3550

395

425

1475

1350    5545     5685       652

2400

3700

420

450

1525

1400    5745     5885       677

2500

3850

445

475

1575

1450    5945     6085       702

2600

4000

470

500

1625

1500    6145     6285       727

2700

4150

495

525

1675

1550    6345     6485       752

2800

4300

520

550

1725

1600    6545     6685       777

2900

4450

545

575

1775

1650    6745     6885       802

3000

4600

570

600

1825

1700    6945     7085       827

3100

4750

595

625

1875

1750    7145     7285       852

3200

4900

620

650

1925

1800    7345     7485       877

3300

5050

645

675

1975

1850    7545     7685       902

3400

5200

670

700

2025

1900    7745     7885       927

3500

5350

695

725

2075

1950    7945     8085       952

3600

5500

720

750

2125

2000    8145     8285       977

3700

5650

745

775

2175

2050    8345     8485      1002

3800

5800

770

800

2225

2100    8545     8685      1027

3900

5950

795

825

2275

2150    8745     8885      1052

4000

6100

820

850

2325

2200    8945     9085      1077

Содержание 940SMT

Страница 1: ...940SMT 940SMT para la naturaleza 100 papel reciclado ist umweltfreundlich 100 Altpapier pour la nature papier recycl 100 for nature recycled paper 100 carta riciclata 100 per la natura...

Страница 2: ...t Mechanical movement risks such as crushing dragging and shearing CE DECLARATION OF CONFORMITY FOR MACHINES DIRECTIVE 89 392 EEC ANNEX II PART B Manufacturer FAAC S p A Address Via Benini 1 40069 Zol...

Страница 3: ...FILE HOUSING PROFILE SLIDING PROFILE CLOSING PROFILE FOR STANDARD AUTOMATED SYSTEM CLOSING PROFILE FOR FREE STANDING AUTOMATED SYSTEM CLOSING PROFILE FOR TELESCOPIC AUTOMATED SYSTEM LEAF ATTACHMENT PR...

Страница 4: ...pply Protection class Anti crushing activation Operating ambient temperature Use frequency Motor power supply Head profile length Opening speed adjustment load free Closing speed adjustment load free...

Страница 5: ...4 ENGLISH ENGLISH 25 21 4 164 5 205 40 5 79 5 71 5 179 5 14 6 10 15 15 50 251 195 Fig 2...

Страница 6: ...5 ENGLISH ENGLISH 14 6 10 15 49 6 135 205 71 5 50 301 35 5 71 5 117 76 2 37 7 50 50 15 15 15 25 195 Fig 3...

Страница 7: ...utomatically activated managed and controlled TheFAACseries940SMTautomatedsystemsaresuppliedfully assembled wiredandtestedintheconfigurationrequestedbythe customerontheorderform orsuppliedasakit Anaut...

Страница 8: ...5245 1227 2400 3700 1020 1050 845 2580 5305 5445 1277 2500 3850 1070 1100 895 2680 5505 5645 1327 2600 4000 1120 1150 945 2780 5705 5845 1377 2700 4150 1170 1200 995 2880 5905 6045 1427 2800 4300 122...

Страница 9: ...900 420 450 180 1380 2905 2765 677 1300 2050 470 500 230 1480 3105 2965 727 1400 2200 520 550 280 1580 3305 3165 777 1500 2350 570 600 330 1680 3505 3365 827 1600 2500 620 650 380 1780 3705 3565 877 1...

Страница 10: ...1100 4545 4685 527 1900 2950 295 325 1275 1150 4745 4885 552 2000 3100 320 350 1325 1200 4945 5085 577 2100 3250 345 375 1375 1250 5145 5285 602 2200 3400 370 400 1425 1300 5345 5485 627 2300 3550 395...

Страница 11: ...10 ENGLISH ENGLISH 36 36 200 12 18 HA 165 LH max 2500 14 6 10 5 INSTALLATION HA LH 15 4 mm 10 Fig 7...

Страница 12: ...11 ENGLISH ENGLISH HA LH 15 4 mm 10 Fig 8 14 6 10 LH max 2500 12 18 135 HA 200...

Страница 13: ...ee securing points Carry out the remaining securing operations every 20 cm on the vertical slots as shown in figure 8 Free standing profile securing with side brackets The automation head profile with...

Страница 14: ...ugs and screws 8 2 Adjustment of the counter roller The carriages are supplied with a counter wheel Adjustment procedurebelow Loosen the two hexagon head screws fig 18 ref and Slide the screw fig 18 r...

Страница 15: ...ightenthecarriage sfixingscrews Fig 25 11 INSTALLATION OF HOUSING FIXING BRACKETS Fit a housing fixing bracket at the end of the head profile opposite the motor unit using the supplied screws and plat...

Страница 16: ...Fully screw the adjuster on the bracket Pull the knob and rotate it through 90 so that it locks on the bracket Thread the cable fig 33 ref inside part leaving the sheath at its limit stop Fit the cab...

Страница 17: ...t it and push it toward the profile until the metal projection fits into the profile seat fig 35 ref Fasten the parachute cables on the housing and on the housing fixing brackets as shown in fig 35 re...

Страница 18: ...17 ENGLISH ENGLISH Fig 40 16 INSTALLATION WITH GRIPPERS FOR GLASS LEAVES HA LH 4 5 18 4 21 10mm To install with the glass leaves grippers refer to the dimensions infigure 40...

Страница 19: ...from the toroidal transformer from the motor and from all accessories routing the cables inside the pre fittedcablesleeves Set motor direction of rotation according to type of door refer to the instru...

Страница 20: ...see table LED ERROR STATUS MEANING OFF normal operating status ON Alarms n 18 20 22 24 execute SETUP SLOW FLASHING current alarm signalling FAST FLASHING setup reset in progress or during setup with...

Страница 21: ...ISABLED DEFAULT no photocell 1 pair of photocells 2 pairs of photocells PSW 2 PSW 1 FAILSAFE VACC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 RX1 TX1 C J5 PSW 2 PSW 1 FAILSAFE VACC 1 2 3 4 5 6 7 8 9 10 11 12 13...

Страница 22: ...ERMINAL BOARD J6 TERMINAL BOARD 1 24V 24V power supply for accessories The total maximum load of the accessories connected to the VACC and 24V inputs must not exceed 700mA 2 OUT 3 default door not clo...

Страница 23: ...Keeper Display as an alternative one photocell only can be set connecting it to the PSW1 input as usual thus disabling the PSW2 input and avoiding the jumper see the SD Keeper programming instruction...

Страница 24: ...nt partial opening and re closing after pause time no effect no effect no effect no effect restarts pause time count total opening and re closing after pause time restarts pause time count partial ope...

Страница 25: ...AGNOSTICS DIAGNOSTICS DIAGNOSTICS DIAGNOSTICS SD Keeper also without display has a diagnostic function which in case of an alarm interrupts normal display of the function every 2 seconds in order to s...

Страница 26: ...range of pause time 0 to 90 sec DOOR OPEN DOOR OPEN DOOR OPEN DOOR OPEN DOOR OPEN The door opens and stays open NIGHT NIGHT NIGHT NIGHT NIGHT The door closes and the lock if present is activated The i...

Страница 27: ...OK key An asterisk on the display indicates the currently active setting To exit programming select the exit function at each level Otherwise after about 2 minutes the display automatically returns to...

Страница 28: ...OK OK OK 4 1 OK OK OK 4 2 OK OK 4 3 4 OK OK OK OK OK OK 5 OK OK 5 1 5 2 OK OK OK BATTERY BATTERY KIT ON OFF NO STANDARD STANDARD BAT OPERATION OPENING NO STANDARD STANDARD CLOSING NIGHT BATT LAST OPER...

Страница 29: ...1 OK OK OK OK OK OK OK 1 1 1 2 1 3 1 4 2 3 4 OK OK OK OK OK OK PASSWORD 0000 ADVANCED MENU PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 OPERATION PARAMETERS CLOSING SPEED OPENING SPEED DECEL WIDTH DECEL...

Страница 30: ...OK OK PASSWORD 0000 ADVANCED MENU PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 incorrect code correct code OPERATION PARAMETERS IN OUT SETUP VARIOUS EXIT CHANGE PASSWORD EMERG 1 OPEN STOP CLOSE SPEED NO...

Страница 31: ...K OK OK OK OK OK OK 3 3 PASSWORD 0000 ADVANCED MENU PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 incorrect code correct code OPERATION PARAMETERS IN OUT SETUP VARIOUS EXIT CHANGE PASSWORD STAND SETUP STA...

Страница 32: ...AND 2 FUN 0 00 00 TIME BAND 5 FUN 0 00 00 TIME BAND 4 FUN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2 FUN 0 00 00 TIME BAND 5 FUN 0 00 00 TIME BAND 4 FUN 0 00 00 TIME BAND 3 FU...

Страница 33: ...at the point where the obstacle had been detected and continues at the slower speed until completed Opening No Standard Opening No Standard Opening No Standard Opening No Standard Opening No Standard...

Страница 34: ...value 0 cm Adjusting range from 0 to 120 cm Closing Closing Closing Closing Closing Sets anticipated time value on the standard deceleration point at the closing stop position Standard value 0 cm Adju...

Страница 35: ...a black out Off Off Off Off Off Elastic kit not installed On On On On On Elastic kit installed Standard Standard Standard Standard Standard When power is restored after a blackout the door remains set...

Страница 36: ...ecute the Setup activate the elastic kit with SD Keeper Display install the accessory mechanically After installation the leaves will open when mains power fails when mains power is restored the elast...

Страница 37: ...charge to perform at least one emergency movement after which the 940SDM control board goes into NIGHT ENERGY SAVING status ENERGY SAVING other than Night operating function VAC is switched OFF SD Ke...

Страница 38: ...night pause time elapses The operation is identical if the person comes from the opposite direction INTERLOCK WITHOUT INTERNAL SENSORS INTERLOCK WITHOUT INTERNAL SENSORS INTERLOCK WITHOUT INTERNAL SEN...

Страница 39: ...RY function was selected for theEMERG2input whenthecontactisrestored RESET is necessary to cancel the signal 3 4 7 EMERG 1 ON Emergency input 1 active This signal is shown whenever the EMERG1 emergenc...

Страница 40: ...execute a new SETUP 2 4 22 The SETUP procedure cannot be completed because excessive friction or excessive leaf weight was detected When this signal is generated the ERROR LED on the 940SDM control bo...

Страница 41: ...alarm in progress connect the SD Keeper to find the alarm and take the appropriate action see the diagnosticsguide G door locked and ERROR LED ON SETUPmustbeexecuted alarm in progress connect the SD K...

Страница 42: ...ra cualquier otro tipo de exigencia de car cter constructivo o comercial Timbro del Rivenditore Distributor s Stamp Timbre de l Agent Fachh ndlerstempel Sello del Revendedor FAAC S p A Via Benini 1 40...

Отзывы: