The reset procedure is necessary following the
occurrence of certain conditions causing the door to stop
operating:
•after an obstacle is detected on 3 successive occasions
during closing/opening when the function STANDARD
OBSTACLE DETECTION (ALARM 8 or ALARM 9) has been
activated;
•after a “with memor y”-configured emergency
command has been activated (see programming
instructions), (ALARM 6 or ALARM 7);
•if, when using a kit lock, an opening malfunction is detected
on the kit.
SPEED CHANGES
SPEED CHANGES
SPEED CHANGES
SPEED CHANGES
SPEED CHANGES
There are 10 speed adjustment levels for opening and
closing.
Level 10 refers to the maximum speed permitted by door
weight, whereas level 1 refers to the corresponding
minimum speed.
CLOSING speed can be adjusted by two push-buttons on
the 940SDM control board (SP-UP and SP-DOWN) if the
SD-Keeper is NOT present.
By using SD-Display, you can change both closing
and opening speed.
Whenever closing speed is changed, the ERROR LED
flashes slowly and the SD-Keeper shows ALARM 1 to report
the need to execute a new Setup, in order to ensure the
electronic anti-crushing device operates correctly.
(1) During standard operation with battery in the
“Night”operating mode, opening is performed by
activating the command key for 3 seconds.
(2) Emerg1 and Emerg 2 inputs can be programmed with
SD-Display to obtain:
- emergency opening;
- emergency closing;
- stop.
Furthermore, command activation can be
programmed:
- with no memory (when the command is de-activated,
the door resumes normal operation);
- with memory (when the command is de-activated, a
Reset is necessary to restore normal operation).
no effect
no effect
restarts pause time
count
total opening and
re-closing after
pause time
restarts pause time
count
partial opening and
re-closing after
pause time
restarts pause time
count
total opening and
re-closing after
pause time
restarts pause time
count
partial opening and
re-closing after
pause time
no effect
no effect
no effect
no effect
restarts pause time
count
total opening and
re-closing after
pause time
restarts pause time
count
partial opening and
re-closing after
pause time
no effect
no effect
no effect
no effect
no effect
no effect
no effect
no effect
starts night pause
time count
total opening and
re-closing after night
pause time
starts night pause
time count
partial opening and
re-closing after night
pause time
starts night pause
time count
total opening and
re-closing after night
pause time
starts night pause
time count
partial opening and
re-closing after night
pause time
(1) total opening
and re-closing after
night pause time
(1) partial opening
and re-closing after
night pause time
no effect
no effect
starts pause time
count
total opening
total opening
total opening
starts pause time
count
total opening
total opening
total opening
total opening
total opening
no effect
immediate closing
immediate closing
no effect
immediate closing
no effect
immediate closing
no effect
immediate closing
no effect
no effect
no effect
IN ANY POSITION
OPEN
OPEN
CLOSED
PARTIALLY OPEN
CLOSED
OPEN
CLOSED
PARTIALLY OPEN
CLOSED
CLOSED
CLOSED
MANUAL
TOTALLY OPEN
TOTAL
AUTOMATIC
TWO-WAY
PARTIAL
AUTOMATIC
TWO-WAY
TOTAL
AUTOMATIC
ONE WAY
PARTIAL
AUTOMATIC
ONE WAY
TOTAL NIGHT
PARTIAL NIGHT
INTERNAL SENSOR
(I-DET)
EXTERNAL SENSOR
(E-DET)
KEY
EMERGENCY
OPENING
(EMERG 2) (2)
EMERGENCY
CLOSING
(2)
DOOR STATUS
OPERATING
FUNCTION
BEHA
BEHA
BEHA
BEHA
BEHAVIOUR UNDER DIFFERENT OPERA
VIOUR UNDER DIFFERENT OPERA
VIOUR UNDER DIFFERENT OPERA
VIOUR UNDER DIFFERENT OPERA
VIOUR UNDER DIFFERENT OPERATING FUNCTIONS
TING FUNCTIONS
TING FUNCTIONS
TING FUNCTIONS
TING FUNCTIONS
This is the default configuration:
Emerg1 ---> Stop/no memory
A pulse (function not shown in the table)
causes immediate stop followed by slow
re-closing after pause time (night pause
time if the Night operating function was
set).
Emerg2 ---> Emergency opening/no memory:
A pulse causes opening followed by re-
closing after pause time.
Emergency commands have priority over all others.