21

ENGLISH

ENGLISH

DESCRIPTION OF TERMINALS

DESCRIPTION OF TERMINALS

DESCRIPTION OF TERMINALS

DESCRIPTION OF TERMINALS

DESCRIPTION OF TERMINALS

TERMINAL BOARD J5

TERMINAL BOARD J5

TERMINAL BOARD J5

TERMINAL BOARD J5

TERMINAL BOARD J5

1

RESET

(NO contact)

Contact closure executes the Reset procedure.
Reset is the function for restoring normal operating
conditions after some types of alarm.

2-5-8-11

- (COM)

Negative for powering accessories (+24V and +Vacc)
and common for contacts

3

EMERG2

(NO default contact)

Emergency command:
in the standard setting, activation causes the door to
open (the door  stays open for as long as the command
is activated).
By using SD-Display, you can program the
operation of this input differently (see programming
instructions).

4

EMERG1

(NO default contact)

Emergency command:
in the standard setting, activation causes the door to
stop (the door stays in stop status for as long as the
command is activated).
By using SD-Display, you can program the
operation of this input differently (see programming
instructions).

6

-FAILSAFE

Negative for powering photocell projectors when the
FAILSAFE function is activated (programmable from SD-
Display).

7-14

+V

ACC

+24V power supply for accessories.
The total maximum load of the accessories connected
to the “+V

ACC

” and “”+24V”  inputs, must not exceed

700mA.

Â

While operating on the battery in the absence of
mains power, when the battery charge drops to a
critical level, Vacc is interrupted for energy saving
purposes.

9

PSW2

(NC default contact)

Input of 2nd  safety photocell
By using SD-Display , you can :
- program the NO contact,
- cut out this input if there are no photocells or if there is
only one photocell (which must therefore be connected
to the PSW1 input).
For the effects the tripped photocell has on this input,
see PSW1.

10

PSW1

(NC default contact)

Input of 1st  safety photocell
By using SD-Display , you can :
- program the NO contact,
- cut out this input if there are no photocells.
Following intervention by the photocell connected to
this input, the door behaves as follows:
OPENING:

no effect

PAUSE:

pause time re-counted

CLOSING:

reverses immediately

12

I-DET

(NO default contact)

Internal sensor input.
By using SD-Display , you can program the NC
contact.

13

E-DET

(NO default contact)

External sensor input.
By using SD-Display , you can program the NC
contact.

J6 TERMINAL BOARD

J6 TERMINAL BOARD

J6 TERMINAL BOARD

J6 TERMINAL BOARD

J6 TERMINAL BOARD

1

+24V

+24V power supply for accessories.
The total maximum load of the accessories connected
to the “+V

ACC

” and “”+24V” inputs, must not exceed

700mA.

2

OUT 3 (default “door not close”)

Open-collector (negative) output (100mA).
In the standard setting, this output is active for as long as
the door is not closed.
By using SD-Display , you can program the
operation of this output differently (see programming
instructions).

3-5-9

- (COM)

Negative for powering accessories (+24V and +Vacc)
and common for contacts.

4

OUT 2 (default : “night courtesy light”)

Open-collector (negative) output (100mA).
In the standard setting, this output is activated for 60 sec.
when the door is commanded to open in NIGHT mode.
By using SD-Display, you can program the
operation of this output differently (see programming
instructions).

6

MONODIR

(NO  contact)

If the SD-Keeper is not installed, closing this contact
activates the “ONE WAY” function.

7

NIGHT

(NO  contact)

If the SD-Keeper is not installed, closing this contact
activates the “NIGHT” function.

8

OPENED

(NO  contact)

If the SD-Keeper is not installed, closing this contact
activates the “DOOR OPEN” function.

10

OUT 1

(“gong” default)

Open-collector (negative) output (100mA).
In the standard setting,  this input is active, while the
photocells are covered, for 1 sec. at 0.5 sec. intervals
until disengaged.
By using SD-Display, you can program the
operation of this output differently (see programming
instructions).

11

KEY

(NO default contact)

Key command:
activation causes the door to open and then re-close
after night pause time elapses.
By using SD-Display , you can program the NC
contact.

12-13

SD-KEEPER

SD-Keeper connection terminals (cable: 2x0.5mm

2

 max

50m).

Â

 Observe indicated polarity.

TERMINAL BOARD J7

TERMINAL BOARD J7

TERMINAL BOARD J7

TERMINAL BOARD J7

TERMINAL BOARD J7

NOT AUS

(NC  contact)

Contact for the emergency push-button (NC) which cuts
power to the motor.

Â

 

If not used, jumper the terminals with a 0.5mm

cable.

MOTOR ROT

MOTOR ROT

MOTOR ROT

MOTOR ROT

MOTOR ROTA

AA

AATION DIRECTION

TION DIRECTION

TION DIRECTION

TION DIRECTION

TION DIRECTION

Set dip-switch n°1 as follows:

DOOR MODEL

DIP-SWITCH N°1

2 LEAVES

OFF

1 LEFT OPENING LEAF

ON

1 RIGHT OPENING LEAF

OFF

Â

The closing direction is established by watching the
automated system head profile from the front and:
- in the case of a double leaf, the LEFT leaf connected
to the bottom section of the belt.
- in the case of a right-opening single leaf, the leaf
always connected to the top section of the belt.
- in the case of a left-opening single leaf, the leaf
always connected to the bottom section of the belt.

Содержание 940SMT

Страница 1: ...940SMT 940SMT para la naturaleza 100 papel reciclado ist umweltfreundlich 100 Altpapier pour la nature papier recycl 100 for nature recycled paper 100 carta riciclata 100 per la natura...

Страница 2: ...t Mechanical movement risks such as crushing dragging and shearing CE DECLARATION OF CONFORMITY FOR MACHINES DIRECTIVE 89 392 EEC ANNEX II PART B Manufacturer FAAC S p A Address Via Benini 1 40069 Zol...

Страница 3: ...FILE HOUSING PROFILE SLIDING PROFILE CLOSING PROFILE FOR STANDARD AUTOMATED SYSTEM CLOSING PROFILE FOR FREE STANDING AUTOMATED SYSTEM CLOSING PROFILE FOR TELESCOPIC AUTOMATED SYSTEM LEAF ATTACHMENT PR...

Страница 4: ...pply Protection class Anti crushing activation Operating ambient temperature Use frequency Motor power supply Head profile length Opening speed adjustment load free Closing speed adjustment load free...

Страница 5: ...4 ENGLISH ENGLISH 25 21 4 164 5 205 40 5 79 5 71 5 179 5 14 6 10 15 15 50 251 195 Fig 2...

Страница 6: ...5 ENGLISH ENGLISH 14 6 10 15 49 6 135 205 71 5 50 301 35 5 71 5 117 76 2 37 7 50 50 15 15 15 25 195 Fig 3...

Страница 7: ...utomatically activated managed and controlled TheFAACseries940SMTautomatedsystemsaresuppliedfully assembled wiredandtestedintheconfigurationrequestedbythe customerontheorderform orsuppliedasakit Anaut...

Страница 8: ...5245 1227 2400 3700 1020 1050 845 2580 5305 5445 1277 2500 3850 1070 1100 895 2680 5505 5645 1327 2600 4000 1120 1150 945 2780 5705 5845 1377 2700 4150 1170 1200 995 2880 5905 6045 1427 2800 4300 122...

Страница 9: ...900 420 450 180 1380 2905 2765 677 1300 2050 470 500 230 1480 3105 2965 727 1400 2200 520 550 280 1580 3305 3165 777 1500 2350 570 600 330 1680 3505 3365 827 1600 2500 620 650 380 1780 3705 3565 877 1...

Страница 10: ...1100 4545 4685 527 1900 2950 295 325 1275 1150 4745 4885 552 2000 3100 320 350 1325 1200 4945 5085 577 2100 3250 345 375 1375 1250 5145 5285 602 2200 3400 370 400 1425 1300 5345 5485 627 2300 3550 395...

Страница 11: ...10 ENGLISH ENGLISH 36 36 200 12 18 HA 165 LH max 2500 14 6 10 5 INSTALLATION HA LH 15 4 mm 10 Fig 7...

Страница 12: ...11 ENGLISH ENGLISH HA LH 15 4 mm 10 Fig 8 14 6 10 LH max 2500 12 18 135 HA 200...

Страница 13: ...ee securing points Carry out the remaining securing operations every 20 cm on the vertical slots as shown in figure 8 Free standing profile securing with side brackets The automation head profile with...

Страница 14: ...ugs and screws 8 2 Adjustment of the counter roller The carriages are supplied with a counter wheel Adjustment procedurebelow Loosen the two hexagon head screws fig 18 ref and Slide the screw fig 18 r...

Страница 15: ...ightenthecarriage sfixingscrews Fig 25 11 INSTALLATION OF HOUSING FIXING BRACKETS Fit a housing fixing bracket at the end of the head profile opposite the motor unit using the supplied screws and plat...

Страница 16: ...Fully screw the adjuster on the bracket Pull the knob and rotate it through 90 so that it locks on the bracket Thread the cable fig 33 ref inside part leaving the sheath at its limit stop Fit the cab...

Страница 17: ...t it and push it toward the profile until the metal projection fits into the profile seat fig 35 ref Fasten the parachute cables on the housing and on the housing fixing brackets as shown in fig 35 re...

Страница 18: ...17 ENGLISH ENGLISH Fig 40 16 INSTALLATION WITH GRIPPERS FOR GLASS LEAVES HA LH 4 5 18 4 21 10mm To install with the glass leaves grippers refer to the dimensions infigure 40...

Страница 19: ...from the toroidal transformer from the motor and from all accessories routing the cables inside the pre fittedcablesleeves Set motor direction of rotation according to type of door refer to the instru...

Страница 20: ...see table LED ERROR STATUS MEANING OFF normal operating status ON Alarms n 18 20 22 24 execute SETUP SLOW FLASHING current alarm signalling FAST FLASHING setup reset in progress or during setup with...

Страница 21: ...ISABLED DEFAULT no photocell 1 pair of photocells 2 pairs of photocells PSW 2 PSW 1 FAILSAFE VACC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 RX1 TX1 C J5 PSW 2 PSW 1 FAILSAFE VACC 1 2 3 4 5 6 7 8 9 10 11 12 13...

Страница 22: ...ERMINAL BOARD J6 TERMINAL BOARD 1 24V 24V power supply for accessories The total maximum load of the accessories connected to the VACC and 24V inputs must not exceed 700mA 2 OUT 3 default door not clo...

Страница 23: ...Keeper Display as an alternative one photocell only can be set connecting it to the PSW1 input as usual thus disabling the PSW2 input and avoiding the jumper see the SD Keeper programming instruction...

Страница 24: ...nt partial opening and re closing after pause time no effect no effect no effect no effect restarts pause time count total opening and re closing after pause time restarts pause time count partial ope...

Страница 25: ...AGNOSTICS DIAGNOSTICS DIAGNOSTICS DIAGNOSTICS SD Keeper also without display has a diagnostic function which in case of an alarm interrupts normal display of the function every 2 seconds in order to s...

Страница 26: ...range of pause time 0 to 90 sec DOOR OPEN DOOR OPEN DOOR OPEN DOOR OPEN DOOR OPEN The door opens and stays open NIGHT NIGHT NIGHT NIGHT NIGHT The door closes and the lock if present is activated The i...

Страница 27: ...OK key An asterisk on the display indicates the currently active setting To exit programming select the exit function at each level Otherwise after about 2 minutes the display automatically returns to...

Страница 28: ...OK OK OK 4 1 OK OK OK 4 2 OK OK 4 3 4 OK OK OK OK OK OK 5 OK OK 5 1 5 2 OK OK OK BATTERY BATTERY KIT ON OFF NO STANDARD STANDARD BAT OPERATION OPENING NO STANDARD STANDARD CLOSING NIGHT BATT LAST OPER...

Страница 29: ...1 OK OK OK OK OK OK OK 1 1 1 2 1 3 1 4 2 3 4 OK OK OK OK OK OK PASSWORD 0000 ADVANCED MENU PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 OPERATION PARAMETERS CLOSING SPEED OPENING SPEED DECEL WIDTH DECEL...

Страница 30: ...OK OK PASSWORD 0000 ADVANCED MENU PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 incorrect code correct code OPERATION PARAMETERS IN OUT SETUP VARIOUS EXIT CHANGE PASSWORD EMERG 1 OPEN STOP CLOSE SPEED NO...

Страница 31: ...K OK OK OK OK OK OK 3 3 PASSWORD 0000 ADVANCED MENU PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 incorrect code correct code OPERATION PARAMETERS IN OUT SETUP VARIOUS EXIT CHANGE PASSWORD STAND SETUP STA...

Страница 32: ...AND 2 FUN 0 00 00 TIME BAND 5 FUN 0 00 00 TIME BAND 4 FUN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2 FUN 0 00 00 TIME BAND 5 FUN 0 00 00 TIME BAND 4 FUN 0 00 00 TIME BAND 3 FU...

Страница 33: ...at the point where the obstacle had been detected and continues at the slower speed until completed Opening No Standard Opening No Standard Opening No Standard Opening No Standard Opening No Standard...

Страница 34: ...value 0 cm Adjusting range from 0 to 120 cm Closing Closing Closing Closing Closing Sets anticipated time value on the standard deceleration point at the closing stop position Standard value 0 cm Adju...

Страница 35: ...a black out Off Off Off Off Off Elastic kit not installed On On On On On Elastic kit installed Standard Standard Standard Standard Standard When power is restored after a blackout the door remains set...

Страница 36: ...ecute the Setup activate the elastic kit with SD Keeper Display install the accessory mechanically After installation the leaves will open when mains power fails when mains power is restored the elast...

Страница 37: ...charge to perform at least one emergency movement after which the 940SDM control board goes into NIGHT ENERGY SAVING status ENERGY SAVING other than Night operating function VAC is switched OFF SD Ke...

Страница 38: ...night pause time elapses The operation is identical if the person comes from the opposite direction INTERLOCK WITHOUT INTERNAL SENSORS INTERLOCK WITHOUT INTERNAL SENSORS INTERLOCK WITHOUT INTERNAL SEN...

Страница 39: ...RY function was selected for theEMERG2input whenthecontactisrestored RESET is necessary to cancel the signal 3 4 7 EMERG 1 ON Emergency input 1 active This signal is shown whenever the EMERG1 emergenc...

Страница 40: ...execute a new SETUP 2 4 22 The SETUP procedure cannot be completed because excessive friction or excessive leaf weight was detected When this signal is generated the ERROR LED on the 940SDM control bo...

Страница 41: ...alarm in progress connect the SD Keeper to find the alarm and take the appropriate action see the diagnosticsguide G door locked and ERROR LED ON SETUPmustbeexecuted alarm in progress connect the SD K...

Страница 42: ...ra cualquier otro tipo de exigencia de car cter constructivo o comercial Timbro del Rivenditore Distributor s Stamp Timbre de l Agent Fachh ndlerstempel Sello del Revendedor FAAC S p A Via Benini 1 40...

Отзывы: