36
WT.025.200.000.DE.IM 0517
Installation
S10k
4.
Note
Before commencing this procedure, ensure that the injector asso-
ciated with the gas feed system is operational, i.e. that the injector
is operating correctly and can be started immediately a gas leak is
detected.
If a leak of gas is detected, close the storage cylinder or header
valves and start-up the injector immediately.
Open all other valves in the gas supply line, including the vacuum
demand valve, to evacuate any gas from the system. Rectify the
leak and re-start the procedure.
1
Activate the gas warning device.
2
Make sure the vacuum demand valve is set to 'OFF'
and
that all valves in the gas supply system are closed.
3
Ensure the auxiliary cylinder valve (if used) is closed and crack
open the main cylinder valve. Test for leaks around the valve
assembly as detailed in the NOTE above. If there are no leaks,
open the main cylinder valve one turn.
4
Open the auxiliary cylinder valve (if used) and then close it
again and test for leaks, to the next valve in the system. If
there are no leaks, fully open the auxiliary cylinder valve.
5
Continue until each valve up to the vacuum demand valve is
tested.
Note
Always open the chlorine container valve slowly and only by one
turn. This is sufficient for normal operation and in an emergency
the valve can be closed faster.
4.11.5
Check of the vacuum demand valve
1
Keep the valves on the chlorine cylinders closed.
Open the valves in the water supply line to the injector and at
the point-of-application.
Open the solenoid valve, start booster pump, if installed.
2
Switch the vacuum demand valve to „operation"
or to
„Standby“ .
Open the control knob at the flowmeter assembly four turns.
The operating knob at the vacuum demand valve must go to
„Empty"
. In this position the red OUT OF GAS warning
indicator, located immediately above the top of the knob, is
Содержание WALLACE & TIERNAN S10k
Страница 1: ...WALLACE TIERNAN GAS FEEDER S10k INSTRUCTION MANUAL ...
Страница 2: ...2 WT 025 200 000 DE IM 0517 S10k Please note Original manual ...
Страница 6: ...6 WT 025 200 000 DE IM 0517 Contents S10k ...
Страница 22: ...22 WT 025 200 000 DE IM 0517 Description S10k 3 ...
Страница 88: ...88 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 Spare parts for the injectors 7 4 1 Injector W3T171367 1 ...
Страница 90: ...90 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 2 Anti syphon injector W3T171368 1 ...
Страница 93: ...S10k Drawings 7 93 ...
Страница 94: ...94 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 3 Injector W3T171369 3 4 ...
Страница 96: ...96 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 4 Antisyphon Injektor W3T171370 3 4 ...
Страница 99: ...S10k Manufacturer declaration 8 99 8 Manufacturer declaration ...
Страница 100: ...100 WT 025 200 000 DE IM 0517 Manufacturer declaration S10k 8 ...