37
uncovered. Then the vacuum is sufficient.
If the vacuum is not sufficient, refer to the chapters „Fault fin-
ding“ and „Maintenance“.
4.12
Commissioning
The following procedures assume that all preparatory steps and
leak tests have been completed satisfactorily.
1
Set the vacuum demand valve to „operation"
.
2
Turn on the water supply to the injector and open the V-notch
plug part-way.
If there are two valves (automatic switchover system) select
one cylinder as the 'duty' supply and set its demand valve to
'operation'. This should create a vacuum which will uncover
the red OUT OF GAS indicator on the front of the vacuum
demand valve.
3
Turn on the gas at the supply cylinder. This should cause the
red OUT OF GAS indicator to disappear.
4
If there are two vacuum demand valves, open the gas cylinder
valve on the standby cylinder approximately one turn and set
the control knob of the valve to the STANDBY
position.
5
Adjust the gas feed at the adjusting knob of the flowmeter
assembly.
Warning!
To avoid possible severe personal injury or equipment damage, do
not open the gas supply container valve more than one turn appro-
ximately. This will permit maximum discharge and also can be tur-
ned off quickly in the event of a gas leak.
4.13
Training the operator
Train the operator for understanding at least in safety, operation
and fault finding.
Note
The operator of the overall system must ensure that only authori-
Содержание WALLACE & TIERNAN S10k
Страница 1: ...WALLACE TIERNAN GAS FEEDER S10k INSTRUCTION MANUAL ...
Страница 2: ...2 WT 025 200 000 DE IM 0517 S10k Please note Original manual ...
Страница 6: ...6 WT 025 200 000 DE IM 0517 Contents S10k ...
Страница 22: ...22 WT 025 200 000 DE IM 0517 Description S10k 3 ...
Страница 88: ...88 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 Spare parts for the injectors 7 4 1 Injector W3T171367 1 ...
Страница 90: ...90 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 2 Anti syphon injector W3T171368 1 ...
Страница 93: ...S10k Drawings 7 93 ...
Страница 94: ...94 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 3 Injector W3T171369 3 4 ...
Страница 96: ...96 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 4 Antisyphon Injektor W3T171370 3 4 ...
Страница 99: ...S10k Manufacturer declaration 8 99 8 Manufacturer declaration ...
Страница 100: ...100 WT 025 200 000 DE IM 0517 Manufacturer declaration S10k 8 ...