S10k
Safety
2.
11
2.3
Safety instructions specific to the S10k system
Warning!
Chlorine gas or sulphur dioxide gas irritates the respiratory tracts.
Contact with chlorine or sulphur dioxide gas in high concentrations
irritates and damages the membranes, respiratory system and the
skin. In extreme cases death can result due to suffocation.
Note
In this manual the use of the S10k system with chorine gas is de-
scribed. When sulphur dioxide or carbon dioxide is used refer to
the safety informations of the gas supplier (e.g. the safety data
sheet).
•
This unit may only be installed and serviced by qualified per-
sonnel who are familiar with the contents of the operating
instructions, works directives and regulations for handling
chlorine.
•
The operators of the gas feed system must be instructed in
safe use of the unit.
•
All personnel coming in contact with the unit must be in full
knowledge of the site operation and emergency procedures
and also regulations for accident prevention.
•
The discharge of chlorine gas from chlorine containers should
not exceed one percent of the nominal container contents per
hour, as otherwise there is the risk that the chlorine container
and the vacuum control valve become iced. Therefore ensure
that a sufficient number of chlorine containers are connected
and open at the same time.
•
When using chlorine barrels the connection valve must be
heated.
•
Always open the chlorine container valve slowly and only by
one turn. This is sufficient for normal operation and in an
emergency the valve can be closed faster. It is also possible
for dirt particles to be pulled off if the value is opened quickly.
These particles then pass through the dirt filter and enter the
valve seat of the vacuum control valve and as a result the
valve no longer closes tightly.
•
When changing the gas cylinders always wear a suitable and
functional gas mask. Practice use of the mask regularly. If
chlorine gas is discharged, only use a breathing system which
is independent of ambient air!
•
Do not tolerate any leakages in the chlorine system. Leakage
points must be sealed immediately as they will become larger
with time if they remain unattended. When inspecting the sys-
tem for leakage always keep your gas mask to hand.
•
All connections and system components must be carefully
Содержание WALLACE & TIERNAN S10k
Страница 1: ...WALLACE TIERNAN GAS FEEDER S10k INSTRUCTION MANUAL ...
Страница 2: ...2 WT 025 200 000 DE IM 0517 S10k Please note Original manual ...
Страница 6: ...6 WT 025 200 000 DE IM 0517 Contents S10k ...
Страница 22: ...22 WT 025 200 000 DE IM 0517 Description S10k 3 ...
Страница 88: ...88 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 Spare parts for the injectors 7 4 1 Injector W3T171367 1 ...
Страница 90: ...90 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 2 Anti syphon injector W3T171368 1 ...
Страница 93: ...S10k Drawings 7 93 ...
Страница 94: ...94 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 3 Injector W3T171369 3 4 ...
Страница 96: ...96 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 4 Antisyphon Injektor W3T171370 3 4 ...
Страница 99: ...S10k Manufacturer declaration 8 99 8 Manufacturer declaration ...
Страница 100: ...100 WT 025 200 000 DE IM 0517 Manufacturer declaration S10k 8 ...