62
WT.025.200.000.DE.IM 0517
Maintenance
S10k
6.
6.8.9
Cleaning the vacuum demand valve
Every year clean the vacuum demand valve. The standard and au-
tomatic switchover units are both cleaned in the same manner.
Warning!
To avoid possible severe personal injury or equipment damage,
shut the gas supply container valve; evacuate all gas from the sys-
tem and release any pressure in the solution discharge line as de-
tailed in Section 5.2.2.
Warning!
Any vertical section of the vent tube may contain chlorine gas/con-
densate.
Pinch the vent tube at its lowest point and then disconnect it from
the demand valve.
Remove and plug the open end. If necessary clear the vent tube
by blowing through it using an inert gas, or allow tube to drain/vent
into room under controlled conditions.
Refer to the drawing in chapter 7.3
1
Loosen the union nut and disconnect the vacuum tubing from
the demand valve outlet. Plug the tube with a rubber stopper
to prevent the entrance of air and moisture while the demand
valve is being cleaned.
2
Loosen the yoke screw and remove the entire vacuum
demand valve to a location where the work is to be done.
Cap the gas supply container valve outlet while not in use.
3
Remove inlet nipple (36). Pay attention not to loosen the valve
body (47), e.g. clamp in a vise.
4
Remove retainer (45) (5 mm key).
5
Remove the spring (34) and stem (33) and hold them under
warm running water to soften and flush away any deposits.
Dry thoroughly.
6
Clean the housing (47) with a towel or cotton stick.
7
Remove the seat (32), refer to next page.
8
Thoroughly dry all parts, reassemble as soon as possible:
Clamp the valve housing (47) with the inlet on top.
Carefully place the stem (33) (needle in front) into the seat
(32).
Place the spring (34).
Place the retainer (45) and screw to the stop.
German version:
Mount the new filter (40), filter holder (39) and ring (125)
Mount the nipple (36) by using a new teflon tape (turn the tape
Содержание WALLACE & TIERNAN S10k
Страница 1: ...WALLACE TIERNAN GAS FEEDER S10k INSTRUCTION MANUAL ...
Страница 2: ...2 WT 025 200 000 DE IM 0517 S10k Please note Original manual ...
Страница 6: ...6 WT 025 200 000 DE IM 0517 Contents S10k ...
Страница 22: ...22 WT 025 200 000 DE IM 0517 Description S10k 3 ...
Страница 88: ...88 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 Spare parts for the injectors 7 4 1 Injector W3T171367 1 ...
Страница 90: ...90 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 2 Anti syphon injector W3T171368 1 ...
Страница 93: ...S10k Drawings 7 93 ...
Страница 94: ...94 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 3 Injector W3T171369 3 4 ...
Страница 96: ...96 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 4 Antisyphon Injektor W3T171370 3 4 ...
Страница 99: ...S10k Manufacturer declaration 8 99 8 Manufacturer declaration ...
Страница 100: ...100 WT 025 200 000 DE IM 0517 Manufacturer declaration S10k 8 ...