Determining the
setpoint trim function
To adjust the control for the setpoint trim function, the Tconst and
Tvar process times must bet entered in the setpoint trim menu.
These times refer to control loop dead times, which on the one
hand are independent of the control variables, and on the other
hand depend proportionally on the control variables.
Tconst
Menu 2
The constant dead time "Tconst" for the setpoint trim is the sum of
the module 2 measurement dead time and possible dosing delays
during the compound-loop-control.
For the calculation, see “Determining combi- control process
times" on page 84.
Tvar
Menu 2
The variable dead time "Tvar" depends on the current flow rate
control variable, the internal diameter of the line and the distance
between where the chlorine is added and the sample water
extracted.
Tvar is entered in the menu for a control variable at 100 % (flow
rate = 100 %).
Tvar determination
procedure
Enter flow rate Wq between 50 % and 100 %.
Set manual dosing rate and start the dead time measurement at
the same time.
Wait until the actual value2 adjusts to the dosing rate and remains
constant.
Stop elapsed measuring time.
Calculate as follows:
Tvar = (measuring time - Tkonst) x 100 % / flow rate Wq %
Содержание WALLACE & TIERNAN MFC
Страница 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Страница 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Страница 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Страница 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Страница 225: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 225 DEPOLOX 5 drawing non pressurised version W3T170031 W3T170031...
Страница 229: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 229 DEPOLOX 5 drawing pressurised version W3T170032 W3T170032...
Страница 233: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 233 VariaSens drawing non pressurised version W3T158742 W3T158742...
Страница 237: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 237 VariaSens drawing pressurised version W3T158756 W3T158756...
Страница 247: ...MFC Certificates 10 247 10 Certificates...
Страница 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 249: ...MFC Certificates 10 249...
Страница 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...
Страница 266: ...266 WT 050 580 000 DE IM 0714 Index MFC 12...