CAN interface
The CAN interface of the MFC serves to control CAN actuators
such as V10K with CAN interface or dosing pumps with CAN
interface, for example.
Individual measured values can also be transmitted to other
measuring and control systems using the CAN bus, e.g. SFC
measuring system for Cl
2
tot./Cl
2
free for displaying the combined
chlorine or SFC-Cl
2
++ with pH value input via CAN bus.
The second control measurement can also be imported with the
CAN interface and the setpoint trim application.
The CAN interface of the MFC is electrically isolated. For
connection to a Wallace & Tiernan CAN bus system, three
terminals and a terminating resistor Rt are integrated in the MFC.
The CAN bus is wired from station to station as a two-wire bus.
The cable of type 1x 2x0.75 mm
2
(part. no. W3T168568) is used
as the installation cable. Stub cables are not permitted.
Do not exceed the maximum line length of 1000 m. The CAN bus
is divided into max. 31 segments. In every segment, there can only
be one CAN master. All devices communicating with one another
must be operated in the same segment.
The bus master in the segment is responsible for controlling the
actuators. The bus master is, for example, MFC, SFC.
CAN slaves include, e.g., dosing pumps with CAN interface, V10K
with CAN interface.
Setting parameters:
Segment address 1...31
CAN address for actuator 0...31
Содержание WALLACE & TIERNAN MFC
Страница 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Страница 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Страница 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Страница 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Страница 225: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 225 DEPOLOX 5 drawing non pressurised version W3T170031 W3T170031...
Страница 229: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 229 DEPOLOX 5 drawing pressurised version W3T170032 W3T170032...
Страница 233: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 233 VariaSens drawing non pressurised version W3T158742 W3T158742...
Страница 237: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 237 VariaSens drawing pressurised version W3T158756 W3T158756...
Страница 247: ...MFC Certificates 10 247 10 Certificates...
Страница 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 249: ...MFC Certificates 10 249...
Страница 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...
Страница 266: ...266 WT 050 580 000 DE IM 0714 Index MFC 12...