MFC
Functions
4.
101
Tconst
Defines the constant dead time in the compound-loop-controller
loop. Consists of the sample water line dead time and the dosing
delay time (for the calculation, see 4.5.3 “Compound-Loop-
Control" on page 81).
Tvar
Defines the variable dead time in the compound-loop-controller
loop. The time to be entered is based on 100 % flow rate (for the
calculation, see 4.5.3 “Compound-Loop-Control" on page 81).
Max.lin.Corr
This parameter monitors changes to already learned dosing
factors.
If new dosing factor changes are learned, which are larger than the
max. linearity correction, this dosing factor is used for all values in
the dosing curve = > initialisation of the curve.
Max.lin.Corr. = 0:
No curve function; only one dosing factor
for all flow rates.
Example:
Max.lin.Corr. = 50 % (based on dosing factor):
Previous dosing factor:
30 %
Newly learned dosing factor:
48 %
max. permissible correction range: 30 ± (50 % from 30 %)
= 30 % ± 15 %
Change in this case:
48 % - 30 % = +18 %
=> The new dosing factor is assumed for the entire curve
because the new dosing factor (+ 48 %) is greater than the
max.lin.Correction (+18 %).
Control factor
Setting the ratio of control range and measuring range, in order to
adjust the control amplification Xp to the process.
Control factor=
(End of measuring range - start of measuring range): Control
range
Example:
Start of measuring range:
pH 4
End of measuring range:
pH 9
Max. process control range:
± 1 pH (=> 2 pH
increments)
=> Control factor =
(9 - 4) : 2 = 2.5
Содержание WALLACE & TIERNAN MFC
Страница 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Страница 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Страница 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Страница 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Страница 225: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 225 DEPOLOX 5 drawing non pressurised version W3T170031 W3T170031...
Страница 229: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 229 DEPOLOX 5 drawing pressurised version W3T170032 W3T170032...
Страница 233: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 233 VariaSens drawing non pressurised version W3T158742 W3T158742...
Страница 237: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 237 VariaSens drawing pressurised version W3T158756 W3T158756...
Страница 247: ...MFC Certificates 10 247 10 Certificates...
Страница 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 249: ...MFC Certificates 10 249...
Страница 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...
Страница 266: ...266 WT 050 580 000 DE IM 0714 Index MFC 12...