MFC
Installation
6.
201
the set 0 % position and the 100 % position.
8
Check the position in a second operation:
Select the "MANUAL" operating mode.
Move to various positions via the MAN.DOS key and check
dosing rate.
Repeat calibration at 0 % and 100 %, if necessary.
9
Determine the running time of the positioner from 0 % to
100 %.
10
Enter the determined running time in the "Cl
2
Dosing" window
under Ty.
Содержание WALLACE & TIERNAN MFC
Страница 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Страница 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Страница 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Страница 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Страница 225: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 225 DEPOLOX 5 drawing non pressurised version W3T170031 W3T170031...
Страница 229: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 229 DEPOLOX 5 drawing pressurised version W3T170032 W3T170032...
Страница 233: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 233 VariaSens drawing non pressurised version W3T158742 W3T158742...
Страница 237: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 237 VariaSens drawing pressurised version W3T158756 W3T158756...
Страница 247: ...MFC Certificates 10 247 10 Certificates...
Страница 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 249: ...MFC Certificates 10 249...
Страница 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...
Страница 266: ...266 WT 050 580 000 DE IM 0714 Index MFC 12...