The following parameters must be set for this operating mode in
menu (2):
•
Band
•
Change
•
Xsh
•
Tconst
•
Tvar
Band
This parameter describes the range within which the compound-
loop-control setpoint 1 can be adjusted by the setpoint trim.
The Band corresponds to the measuring range in percent. The
compound-loop-control setpoint may, therefore, move within the
range of set Band or setpoint2 - Band.
Example:
Measuring range = 2.0 mg/l free chlorine
Setpoint 2
= 1.00 mg/l
Setpoint range
= 20 %
The setpoint range of 20 % defined here corresponds to the
measuring range, (i.e. 20 % of 2.00 mg/l = 0.40 mg/l). Therefore,
the setpoint may move in the range of 0.60 to 1.40 mg/l.
If the setpoint trim function records a value outside this Band, the
maximum or minimum value of the Band is entered (in this
example: 0.60 mg/l and 1.40 mg/l).
Change
This parameter describes the modification factor, by which the
compound-loop-control setpoint 1 should change in the event of a
control deviation. The value corresponds to the control deviation in
percent.
Example:
Measured value
=
0.60 mg/l free chlorine
Setpoint
= 1.00
mg/l
Change
= 50
%
Error
= 0.40
mg/l
The setpoint is increased by 0.20 mg/l, which reflect 50 % of the
error.
Xsh
This parameter describes a neutral range for the measured value
of module2 and is indicated in percent on the measuring range end
value. If the measured value in module2 is within this range around
the setpoint, the setpoint trim function is inactive. If the measured
value of module2 is outside this neutral range, the setpoint trim
function is active and optimises the setpoint of module1.
Содержание WALLACE & TIERNAN MFC
Страница 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Страница 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Страница 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Страница 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Страница 225: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 225 DEPOLOX 5 drawing non pressurised version W3T170031 W3T170031...
Страница 229: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 229 DEPOLOX 5 drawing pressurised version W3T170032 W3T170032...
Страница 233: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 233 VariaSens drawing non pressurised version W3T158742 W3T158742...
Страница 237: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 237 VariaSens drawing pressurised version W3T158756 W3T158756...
Страница 247: ...MFC Certificates 10 247 10 Certificates...
Страница 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 249: ...MFC Certificates 10 249...
Страница 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...
Страница 266: ...266 WT 050 580 000 DE IM 0714 Index MFC 12...