Instruction Manual ZHK
V07-21.0
65/140
NOTICE!
Attention:
Filters must be pushed completely to the back, so that all filters fit
closely to the filter frame and an air bypass is avoided. Important: Examine if the
first filter fits closely to the sealing. (
Figure 148:
Pushing and clamping of the fil-
ters to the rear wall
Figure 149:
Check, if filter lie on the sealing
5.4.4 HEPA filters
If a sealant is not included in the filter manufacturer delivery, a suitable sealing is delivered (loose)
by EUROCLIMA. This sealing is then to fix on the filter cell, or alternatively on the filter frame.
The following two installation frames are available for HEPA filters:
Standard HEPA filter frame
The filter mounting frame is mounted in the AHU housing. This fulfils the pre-filter function for ter-
minal HEPA filters.
During installation, the bracket must first be hooked in and then the filter cell inserted, see
Figure 150:
Attaching the brackets
Figure 151:
Inserting the filter cell
Depending on the filter type, one of the two systems described below is used for fixing the filter
frames:
1. Filter types with frames made of wood-based materials shall be fixed with tensioning corners as
and
Содержание ZHK
Страница 1: ...ZHK INSTRUCTION MANUAL...