Instruction Manual ZHK
86/140
V07-21.0
DANGER!
Attention
: Danger due to leakage current!
Leakage current exceeds 3.5 mA. It is the task of the operator or the certificated
electrician to provide a suitable earth (see
7.1 Connecting to an external pro-
of the AHU. An incompetently fitted earth of the fre-
quency converter could lead to death or to serious injuries.
In addition to 1) or 2) full motor protection with PTC (thermistor)
As standard a PTC thermistor (specified in the technical data sheet as PTC) is used for:
-
Motors for belt-driven fans capacity >= 11 kW
-
As an option for smaller capacities available
-
For all plug fan motors
NOTICE!
To prevent motor damage, the PTC must be connected to a PTC relay. The PTC
relay does not replace the motor protection switch or circuit breaker and is
needed in addition. The connection to a PTC relay is a prerequisite for the guar-
anteed warranty of the product in case of winding damage.
The full motor protection consists of temperature sensors and a PTC relay (on site). On frequency
converters, this function is integrated.
How it works: For single-speed three-phase AC motors, 3 temperature sensors are installed in se-
ries on the exhaust air side of the motor in the winding head. At 135 °C, a sharp increase of re-
sistance occurs, which switches the PTC relay off. For an example of the connection diagram refer
to
Figure 183:
Wiring diagram for thermistors
The full motor protection switches off the motor in case of:
-
Overload of the motor
-
Poor cooling
-
Bearing damage
-
Block of the rotor
-
Winding problems
NOTICE!
Voltages must not exceed 5 V at the temperature sensor. This leads to its de-
struction!