Instruction Manual ZHK
V07-21.0
7/140
Legend for the AHU size
Example 15/6: the first index (15) corresponds to the clear width, the second index (6) to the clear
height. According to the following table, the dimensions in mm are
→
15/6 = 1525 x 610 mm (clear
width x clear height)
This information applies both to the ratios of the supply air and the exhaust air.
1.4 Intended use / foreseeable misuse
1.4.1 Intended use
The AHU is used, depending on the chosen purpose for
-
transportation and conditioning of air in and out of habitable buildings or vessels.
-
creation of a desired room air quality in living and work spaces
-
creation of an acceptable comfort or desired working conditions
-
depending on the AHU type, the air conditioning is done primarily by
o
Air change
o
Control of air temperature and air humidity
o
Filtration of normal polluted air
o
Filtration at specific requirements (clean room and so on)
The AHU is suitable for
-
operation in the range of the agreed design data
-
an ambient air temperature range of
–
20 °C to + 60 °C at installation site, if electrical/electronic
components are mounted on the outside of the AHU, then + 40 °C maximum
-
a minimum temperature of the transported air of -20 °C (if necessary, freeze protection
measures must be installed)
-
a maximum temperature of the transported air of +60 °C
-
inside the AHU at motors and other electrical/electronic components up to +40 °C maximum
The AHU must be used as intended and in the appropriate environment, if not this is categorized
as misuse of the device. If there is any case of AHU misuse, then the warranty/ guarantee be-
comes null and void, which means immediate expiration of the complete warranty and / or guaran-
tee claims.
The operation within other conditions must be agreed in writing. Unless otherwise agreed, the de-
sign of the AHU is for a nominal density of the air of 1,20 kg/m³.
Design responsibility for AHUs, are built according to customer specifications
AHUs from EUROCLIMA as described in this manual are designed, built and delivered according
to customer requirements and specifications. Therefore, EUROCLIMA can select and offer a num-
ber of materials and components, which are varied in quality levels.
Generally, a HVAC specialist, knowing the exact application of the AHU, generates a specification,
in which customer requirements for the AHU are defined. The properties of the AHU, specified by
EUROCLIMA, are agreed with the customer and are stated on the technical data sheets and draw-
ing of the AHU.
Index
3
4
6
9
12
15
18
21
24
Dimension (mm)
305
457,5
610
915
1220
1525
1830
2135
2440
Index
27
30
33
36
39
42
45
48
Dimension (mm)
2745
3050
3355
3660
3965
4270
4575
4880
Содержание ZHK