W
ATLOW
®
EZ-ZONE
®
RMZ4
-
70
-
E
THER
CAT
®
A
DAPTER
17
RMZ4
S
PECIFICATIONS
Feature
Specification
Supply Voltage
20.4 to 30V AC/DC 50/60 Hz
Compliant with SEMI F47-200, Figure R1-1 voltage sag
External supply should comply with Class 2 or SELV
Wire on slot “C” connector
Power
4 Watts Max, 14 VA
Environmental
-18 to 65°C operating
-40 to 85°C storage
0 to 90% RH, non-condensing
Agency Approvals
UL /EN 61010 Recognized; c-UL C22.2 #61010; File #
E185611 QUYX, QUYX7
ANSI/ISA 12.12.01-2012 hazardous locations Class 1 Div.
2
EN60529 IP20
RoHS by design
W.E.E.E.
FM Class 3545 on connected RML, RMC, ST module
CE
Weight
200 grams (7 oz) without adder cards
Wiring
Slot “C” connector
Touch-safe removable 12 to 30 AWG
Torque 0.8 N-m (7.0 lb-in) right angle
Mounting
DIN-rail spec. EN50022 35x7.5mm
Control Loops
48 max, set by model number
Process Alarms
1 per control loop
Deviation Alarm
1 per control loop
Connected EZ-ZONE RM controllers
15 max
Compatible EZ-ZONE RM types
RMC – Sensor inputs, outputs, limits, CT
RME – Outputs, CT
RMS – Sensor inputs, outputs
RMH – Sensor inputs
RML - Limits
Connected EZ-ZONE ST or PM controllers
8 max
Heat Control Mode
PID
Cool Control Modes
PID / On-Off
Control Update Tate
10 Hz
Ramp to Set Point
Programmable in degrees per minute
Current Sense
One configurable heater current sensor per control loop
(resident in RME and RMC modules)
Содержание EZ-ZONE RMZ4
Страница 16: ...WATLOW EZ ZONE RMZ4 16 ETHERCAT ADAPTER FIGURE 7 MODBUS MASTER AND SLAVE RJ 12 CONNECTOR PINOUT ...
Страница 23: ...WATLOW EZ ZONE RMZ4 23 ETHERCAT ADAPTER ...
Страница 24: ...WATLOW EZ ZONE RMZ4 24 ETHERCAT ADAPTER ...
Страница 53: ...WATLOW EZ ZONE RMZ4 53 ETHERCAT ADAPTER FIGURE 12 ALARM GROUP EXAMPLE ...
Страница 74: ...WATLOW EZ ZONE RMZ4 74 ETHERCAT ADAPTER ...