8.16
A
LARM
G
ROUPS
Each loop has a process and deviation alarm. These can be individually mapped to output. However many
application want to trigger an output is
any
of a group of alarms is active. The RMZ4 provides 8 alarm groups
to facilitate alarm aggregation. Each group may be mapped to a digital output. The group provides a means to
pick which active alarms are part of the group from any control loop. The groups are configured in the 0x5F00
object. The control loops are assigned a group in the 8 Pick Lists 0x5F01 to 0x5F08. The groups are not
slot/module based since they are not associated one to one with the control loops. Groups can be used to
energize a contactor when all control loops associated with that power distribution bus are operating properly.
Mapping and Configuration
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Alarm Group 1 Logic
0x5F00
0x69
0x11
Specifies the logic state taken when any of the
picked alarms is active.
0 = If any alarm is condition matches the pick
for the group, the group will be FALSE.
1 = If any alarm is condition matches the pick
for the group, the group will be TRUE.
Alarm Group 1 Output Bus
0x5F00
0x69
0x12
Defines which bus hosts the digital alarm
group 1 output. This is only applicable to EZ-
ZONE RM device.
0 = Unused
1 = RM back plane.
Alarm Group 1 Output
Zone
0x5F00
0x69
0x13
Defines which zone on the bus hosts the
digital alarm group 1 output
Alarm Group 1 Output
Instance
0x5F00
0x69
0x14
Defines which output in the zone implements
the digital alarm group 1 output.
Alarm Group 2 Logic
0x5F00
0x69
0x15
Specifies the logic setting for alarm group 2.
Alarm Group 2 Output Bus
0x5F00
0x69
0x16
Defines which bus hosts the alarm group 2
output.
This is only applicable to EZ-ZONE RM device.
0 = Unused
1 = RM back plane
Alarm Group 2 Output
Zone
0x5F00
0x69
0x17
Defines which zone on the bus hosts the alarm
group 2 output
Alarm Group 2 Output
Instance
0x5F00
0x69
0x18
Defines which output in the zone implements
the digital alarm group 2 output.
Alarm Group 3 Logic
0x5F00
0x69
0x19
Specifies the logic setting for alarm group 3.
Alarm Group 3 Output Bus
0x5F00
0x69
0x1A
Defines which bus hosts the alarm group 3
output.
This is only applicable to EZ-ZONE RM device.
0 = Unused
1 = RM back plane
Содержание EZ-ZONE RMZ4
Страница 16: ...WATLOW EZ ZONE RMZ4 16 ETHERCAT ADAPTER FIGURE 7 MODBUS MASTER AND SLAVE RJ 12 CONNECTOR PINOUT ...
Страница 23: ...WATLOW EZ ZONE RMZ4 23 ETHERCAT ADAPTER ...
Страница 24: ...WATLOW EZ ZONE RMZ4 24 ETHERCAT ADAPTER ...
Страница 53: ...WATLOW EZ ZONE RMZ4 53 ETHERCAT ADAPTER FIGURE 12 ALARM GROUP EXAMPLE ...
Страница 74: ...WATLOW EZ ZONE RMZ4 74 ETHERCAT ADAPTER ...