Analog Retransmit Output
Electrical High
0x4nn1
0x68
0x2B
This is the electrical analog output value
associated with the Scale High value
(0x4nn1:26) such as 10V or 20mA.
Analog Retransmit Output
Electrical Low
0x4nn1
0x68
0x2C
This is the electrical analog output value
associated with the Scale High value
(0x4nn1:27) such as 0V or 4mA.
8.10
A
LARM
O
UTPUTS
Mapping Process Alarm 1
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Process Alarm 1 Bus
0x4nn0
0x67
0x2B
Specifies the communication bus connects to
the outputs for the process alarm 1.
0 = Unused
1 = RM
2 = Legacy ST/PM
3 = Modbus SL-10
Process Alarm 1 Zone
0x4nn0
0x67
0x2C
Defines which device zone/address on the
bus provides the process alarm 1.
Process Alarm 1 Instance
0x4nn0
0x67
0x2D
Defines which output in this device provides
the process alarm 1 output.
Mapping Deviation Alarm 2
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Deviation Alarm 2 Bus
0x4nn0
0x67
0x2E
Specifies the communication bus connects to
the outputs for the deviation alarm 2
0 = Unused
1 = RM
2 = Legacy ST/PM
Deviation Alarm 2 Zone
0x4nn0
0x67
0x2F
Defines which device zone/address on the
bus provides the output for deviation alarm
2.
Deviation Alarm 2 Instance
0x4nn0
0x67
0x30
Defines which output in this device provides
the output for deviation alarm 2.
Configuring
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Alarm 1 Enable
0x8nn0
0x6D
0x14
0 = Disable the process alarm
1 = Enabled the process alarm
Содержание EZ-ZONE RMZ4
Страница 16: ...WATLOW EZ ZONE RMZ4 16 ETHERCAT ADAPTER FIGURE 7 MODBUS MASTER AND SLAVE RJ 12 CONNECTOR PINOUT ...
Страница 23: ...WATLOW EZ ZONE RMZ4 23 ETHERCAT ADAPTER ...
Страница 24: ...WATLOW EZ ZONE RMZ4 24 ETHERCAT ADAPTER ...
Страница 53: ...WATLOW EZ ZONE RMZ4 53 ETHERCAT ADAPTER FIGURE 12 ALARM GROUP EXAMPLE ...
Страница 74: ...WATLOW EZ ZONE RMZ4 74 ETHERCAT ADAPTER ...