W
ATLOW
®
EZ-ZONE
®
RMZ4
-
47
-
E
THER
CAT
®
A
DAPTER
8.14
D
IRECT
A
NALOG
I
NPUT
Direct analog inputs are any sensor or process input in the RM system. These can be monitored directly from
the EtherCAT network. The point may be mapped to User PDO. Make sure this input is not used by a control
loop or limit. The configurations would interfere with each other.
Mapping
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Direct Analog Input Bus
0x4nn0
0x67
0x3B
Specifies the communication bus that connects
to the analog input module.
This is only applicable to EZ-ZONE RM device.
0 = Unused
1 = RM back plane.
Direct Analog Input Zone
0x4nn0
0x67
0x3C
Defines which device zone/address on the bus
provides the analog input.
Direct Analog Input
Instance
0x4nn0
0x67
0x3D
Defines which input in this device provides the
analog input.
Configuring
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Direct Analog Input Sensor
Type
0x4nn1
0x68
0x32
This is the sensor type for the direct digital
input.
0 = TC
1 = RTD100
2 = RTD1000
3 = 4-20mA
4 = 0-20mA
5 = 0-10V
Direct Analog Input TC
Type
0x4nn1
0x68
0x33
This is the sensor type for the direct digital
input.
0: K 1: J 2: T 3: E
4: N 5: R 6: S 7: B
8: C 9: D 10: F
Process Scale High for
Direct Analog Input
0x4nn1
0x68
0x34
This is the input value associated with the high
electrical signal such as 0V or 4mA.
Process Scale Low for
Direct Analog Input
0x4nn1
0x68
0x35
This is the input value associated with the low
electrical signal such as 0V or 4mA.
Using
Содержание EZ-ZONE RMZ4
Страница 16: ...WATLOW EZ ZONE RMZ4 16 ETHERCAT ADAPTER FIGURE 7 MODBUS MASTER AND SLAVE RJ 12 CONNECTOR PINOUT ...
Страница 23: ...WATLOW EZ ZONE RMZ4 23 ETHERCAT ADAPTER ...
Страница 24: ...WATLOW EZ ZONE RMZ4 24 ETHERCAT ADAPTER ...
Страница 53: ...WATLOW EZ ZONE RMZ4 53 ETHERCAT ADAPTER FIGURE 12 ALARM GROUP EXAMPLE ...
Страница 74: ...WATLOW EZ ZONE RMZ4 74 ETHERCAT ADAPTER ...