![EtherCAT EZ-ZONE RMZ4 Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/ethercat/ez-zone-rmz4/ez-zone-rmz4_user-manual_2432549048.webp)
W
ATLOW
®
EZ-ZONE
®
RMZ4
-
48
-
E
THER
CAT
®
A
DAPTER
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Direct Analog Input Value
0x2nn0
0x65
0x16
This is the most recent, live value of this input.
This value can be mapped to the User PDO.
8.15
D
IRECT
A
NALOG
O
UTPUT
Direct digital outputs are controlled directly from the EtherCAT network. They are not controlled by algorithms
in the RM system. This allows any analog output in the RM system to be controlled remotely. The value can be
mapped to User PDO. This output share scaling with the cool analog output.
Mapping
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Direct Analog Output Bus
0x4nn0
0x67
0x3E
Specifies the communication bus connects to
the analog outputs for the cooling action.
This is only applicable to EZ-ZONE RM device.
0 = Unused
1 = RM back plane.
Direct Analog Output Zone
0x4nn0
0x67
0x3F
Defines which device zone/address on the bus
provides the analog cooling output.
Direct Analog Output
Instance
0x4nn0
0x67
0x40
Defines which output in this device provides
the analog cooling output.
Configuring
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Analog Cool Output
Electrical High
0x4nn1
0x68
0x26
This is the analog output value associated with
100% cool power such as 10V or 20mA
Analog Cool Output
Electrical Low
0x4nn1
0x68
0x27
This is the analog output value associated with
0% cool power such as 0V or 4mA.
Using
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Direct Analog Output Value
0x3nn0
0x66
0x14
The output can be set here via SDO. This value
can be mapped to the User PDO.
Содержание EZ-ZONE RMZ4
Страница 16: ...WATLOW EZ ZONE RMZ4 16 ETHERCAT ADAPTER FIGURE 7 MODBUS MASTER AND SLAVE RJ 12 CONNECTOR PINOUT ...
Страница 23: ...WATLOW EZ ZONE RMZ4 23 ETHERCAT ADAPTER ...
Страница 24: ...WATLOW EZ ZONE RMZ4 24 ETHERCAT ADAPTER ...
Страница 53: ...WATLOW EZ ZONE RMZ4 53 ETHERCAT ADAPTER FIGURE 12 ALARM GROUP EXAMPLE ...
Страница 74: ...WATLOW EZ ZONE RMZ4 74 ETHERCAT ADAPTER ...