W
ATLOW
®
EZ-ZONE
®
RMZ4
-
58
-
E
THER
CAT
®
A
DAPTER
10.3
D
EFAULT
R
X
PDO
This is the data received by the controller every scan cycle (usually 1-10ms as controlled by the master). It is
configured at index 0x1600 predefined standard data points and 0x1601 for user defined data points for loop1,
0x1602/0x1603 for loop2, etc. The parameters in the user defined (odd numbered) PDO can be changed by
changing the Entry Index and Entry Sub Index contained in the PDO sub index but this is global, not on a per-
module basis. The even PDOs are a standard set defined by the Standard Device Profile (SDP) and are fixed.
PDO Sub Index
Name
PDO Entry Index
PDO Entry Sub Index
PDO Entry Name
0x01
Sub Index 001
0x7nn0
0x11
Target Set Point Loop nn
0x02
Sub Index 002
0x7nn0
0x13
Clear Alarms Loop nn
0x03
Sub Index 003
0x7nn0
0x12
Forced MV Loop nn
0x04
Sub Index 004
0x7nn0
0x02
Control Mode Loop nn
0x05
Sub Index 005
0x7nn0
0x01
Control State Loop nn
10.4
D
EFAULT
T
X
PDO
This is the data transmitted by the controller every scan cycle (usually 1-10ms as controlled by the master). Is it
configured at index 0x1A00 for loop1, 0x1A02 for loop2, etc.
PDO Sub Index
Name
PDO Entry Index
PDO Entry Sub Index
PDO Entry Name
0x01
Sub Index 001
0x6nn0
0x11
Process Value Loop nn
0x02
Sub Index 002
0x6nn0
0x17
Alarm Condition Loop nn
0x03
Sub Index 003
0x6nn0
0x12
Manipulated Value (Control Output) Loop nn
0x04
Sub Index 004
0x6nn0
0x16
Controlling Set Point Loop nn
0x05
Sub Index 005
0x6nn0
0x01
Actual Control State Loop nn
0x06
Sub Index 006
0x6nn0
0x03
Sensor Error Loop nn
0x07
Sub Index 007
0x6nn0
0x02
Actual Control Loop Mode Loop nn
10.5
U
SER
R
X
PDO
Users can define their own PDO data in the 0x1601, 0x1603, 0x1605… Any RX map-able PDO can be placed in
this area. Each module/slot can have its own User RxPDO set. The only constraint is that the parameters must
be part of this Loop/Module.
10.6
U
SER
T
X
PDO
Users can define their own PDO data in the 0x1A01, 0x1A03, 0x1A05… Any TX map-able PDO can be placed in
this area. Each module/slot can have its own User TxPDO set. The only constraint is that the parameters must
be part of this Loop/Module.
11
D
EVICE
N
ET
®
P
ROTOCOL
Содержание EZ-ZONE RMZ4
Страница 16: ...WATLOW EZ ZONE RMZ4 16 ETHERCAT ADAPTER FIGURE 7 MODBUS MASTER AND SLAVE RJ 12 CONNECTOR PINOUT ...
Страница 23: ...WATLOW EZ ZONE RMZ4 23 ETHERCAT ADAPTER ...
Страница 24: ...WATLOW EZ ZONE RMZ4 24 ETHERCAT ADAPTER ...
Страница 53: ...WATLOW EZ ZONE RMZ4 53 ETHERCAT ADAPTER FIGURE 12 ALARM GROUP EXAMPLE ...
Страница 74: ...WATLOW EZ ZONE RMZ4 74 ETHERCAT ADAPTER ...