Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
6. APPENDIX
Appendix A
- Possible error messages
Text Messages
Description
Alarm
Fire sign
al from detector.
Loop Device Type Error
A different than the expected type of device has been detected at the address.
Loop Device Fault
The device does not respond (lost or damaged).
Double Address
More than one device with the same address in the loop.
PreAlarm
Fire signal from detector in
2DEVICES
zone.
Evacuate
Activated Call Point or EVACUATE button on the panel.
Loop Device Input Fault
Fault in loop device input.
Loop Device Output Fault
Fault in loop device output.
Loop Device Sounder Fault
Fault in loop sounder output (short-circuit or interruption).
Fault Routing - Fault
Fault at problem output (short-circuit or interruption).
Fire Brigade - Fault
Fault at fire output (short-circuit or interruption).
Fire Protection - Fault
Fire protection fault (short-circuit or interruption).
Loop Device Disabled
Loop device has been disabled.
Chamber Fault
Fault in the detector.
Clean Me Now
Dirty detector chamber.
Test Fire
Fire signal from tested detector.
Signal Blockage
Signal blockage in linear detector.
Hi Signal
Too high a signal in linear detector.
Drift Alert
Sensor compensation limit reached.
Earth Fault
Resistive connection between some signals and earth < 10k.
Battery Low
Low battery.
Charger Fault
Fault in the charging device.
Battery Loss
Loss of electric battery supply.
AC Loss
Loss of mains supply.
Sounder Fault
Fault at sounder output (short-circuit or interruption).
AUX24V Fault
Short-circuit.
AUX12V Fault
Short-circuit.
Periphery Device Fault
The device does not respond (lost or damaged).
Periphery Device Type Error
A different than the expected type of device has been detected at the address.
External Power Supply Fault
External power supply fault (low battery, loss of battery, charger fault, loss of mains
or earth leak).
External Power Supply Loss
Loss of external power supply.
Zone Disabled
The zone has been disabled.
Zone in Test
The zone is in test mode.
Sounder Disabled
The sounders have been disabled.
Fire Brigade Output Disabled
The fire output has been disabled.
Fire Protection Output
Disabled
The fire protection has been disabled.
Fault Output Disabled
The fault output has been disabled.
Reset
Resetting of the panel.
Silence Alarm
Sounders silencing.
Ram Error
RAM memory error.
Flash Error
Flash memory error.
Panel Fault
Fault in the connection with another panel (when two or more panels are connect-
ed in a network).
Double IP address
Doubling of an IP address.
Double Panel number
Doubling of the panel number (when two or more panels are connected in a net
-
work).
Double IP address and Panel
number
Doubling of the IP address and the panel number (when two or more panels are
connected in a network).
New Periphery Devices
Found
New periphery devices have been detected.
New Loop Devices Found
New loop devices have been detected.