40
Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
•
ZONE
- Number of zone and event for activation.
Choosing the
Zone
type of the input will add a new field
Function
- Fig. Screen 15. After choosing this field the pos
-
sible zone events will be displayed on the screen.
Choose the
MORE
button. Set the zone number, from 1 to 96, in the
screen “
INPUT Parameters - zone”.
Fig. Screen 15 - Menu for zone events introducing.
• ALARMS -
Enter a number for activated alarms from a zone. Choose the
MORE
button. Set the zone number (1-96)
and alarms counter (1-9). When the alarms counter set number is reached for the set zone number, the input will be
activated.
•
TIME
- Device input activation time. Choose the
MORE
button. Set the hour, minutes and day of the week when the
input has to be activated, in the screen “
INPUT Parameters - time”.
Every day of the week could be enabled or disabled
in a separate screen.
•
DATE
- Device input activation date. Choose the
MORE
button. Set
the year, month and the day when the input has
to be activated
, in the screen “
INPUT Parameters - date”
Enter.
•
ACTION
- Device input activation action.
Choosing the
Action
type of the input will add a new field
Function
- Fig. Screen 15. The possible actions are as fol
-
lows:
-
SILENCE buZZER
- SILENCE SOuNDER
- RESET
- SOuNDER ON
- FIRE bRIGADE ON
- FAuLT ROuTING ON
- FIRE PROTECTION ON
•
GENERAL
- General status which will activate the input of the device.
Choosing the
General
type of the input will add a new field
Function
- Fig. Screen 15. The possible statuses can be:
- COMMON FIRE
- COMMON PREALARM
- COMMON FAuLT
- SYSTEM FAuLT
- DISAbLED
- TEST
• NETWORK -
Panel / repeater number and output number, to which the input shall be attached. Choose the
MORE
button. Set the parameters in the screen “
INPUT Parameters - network”:
- INPUT Number.
Enter a number from 1 to 128.
-
PANEL/ REPEATER Number.
Enter a number from 1 to 32.
•
Zone Group
- Activation from a zone in fire alarm or fault included in a group. To enter the number of the group
press MORE button. In the new menu screen the installer can also set the logic for operation OR/ AND.
Choosing the
Zone Group
type of the input will add a new field
Function
. The possible actions are as follows:
-
ZONE FIRE
- ZONE FAuLT
All changed parameters are confirmed and saved by pressing the APPLY button in the upper left corner of the
screen.