Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
2.2.5 Loop Expander
The MAGPRO96 fire panel operates with MAGPRO96-L250 loop controller (
MAGPRO communication protocol
).
The Loop Controller (Figure 14) realizes the connection between the I/O Module and devices connected to the com
-
munication line. The Loop Expander has two basic functions: 1. Gathers data from the devices in the communication
line and transfers it to the I/O Module; 2. Receives commands from the I/O Module and transfers them to the devices
connected in the communication line.
Every MAGPRO96-L250 Loop
provides up to 250 devices.
The maximum current consumption of the devices in the communication line is I
max
= 500mA. If the consumption ex
-
ceeds this value an over-load protection would be turned on.
In the configuration of analogue-addressable fire panel MAGPRO96 could be mounted up to 4 loop controllers.
1
- Interface connector for connecting the Loop expander to the I/O Module.
2
- Interface connector for connecting second loop expander.
Figure 14. General view of Loop Expander and an example for connecting devices to it.
Adding of loop expander in the configuration of the fire panel MAGPRO96
ATTENTION:
DO NOT ADD OR REMOvE LOOP ExPANDERS to the fire panel configuration WHEN
THE MAIN AND bACkuP POWER SuPPLIES ARE ON
!
First
Loop Expander
I/O Module
Second
Loop Expander
1
- Connect the interface connectors of the first and the second loop expanders.
2
- Fix the second loop expander with supplied bolts in the kit to the metal box of the fire panel.
Figure 15. Connecting of a second loop expander in the fire panel configuration.
Note:
The method of adding third and forth loop expander is analogical to that shown on Fig. 15.
Loop Expander
I/O Module
First
Loop Expander
Second
Loop Expander