14
Addressable Fire Panel MAGPRO96
- Installation and Programming Manual
2.2.7 Main Power Source
Red LED for
indication of
V.
220
Black
Black
Yellow-green
Black
Black
Y
ellow-green
Fuse
F-Type
2
А
Main
Power
Source
LED-indication for the status
of Main Power Source.
Terminal block for
external power supply.
1
2
3
4
5
6
1
2
3
4
Figure 17. General view of the power source and the terminal.
LED-indication of the power source
LED
Function
Description
1
AC LOSS
Main power supply loss 220V.
2
Charger Fault
Problem with the battery charging.
3
BATT LOSS
Battery loss.
4
BATT Low/ Ri
Discharged battery/ High internal resistance Ri of the accumulator battery.
5
EARTH FAULT Resistance to GND ≤ 10kΩ.
6
Rx / Tx
Shows the communication with the panel.
Terminal Block for connecting to external power supply.
Terminal
Function
Description
1
GND
Input for connecting of external power supply EARTH.
2
FAULT OUT
Fault output, turns on when a problem with the main power supply oc
-
curred. Connect it to the input (Fault In) of the external power supply.
3
FAULT IN
Input for connecting the Fault output of the external power supply.
4
+13.8V
External power supply input.
Before the mains supply is switched on, check the correct connection of each loop, sounder or any
other input or output.
LED indication for the status
of Main power source
Terminal block for
external power supply
Main
Power
Source
Fuse 2
AF type
Red LED for
220V indication
Black
Black
Yellow-green
Black
Black
Yellow-green