After the relay modules are configured, use the same procedure to configure the display
modules and if included the alarm modules.
Fig. 6.11 – Configuration of the display modules
After the configurations are completed and the status LEDs on the field devices are all
flashing slowly (one flash every 10 seconds), close all the front covers and go onto the
"ASSIGNMENT" operation between the input field devices (gas detectors and alarm
modules) and the command and display field devices (relay modules and display modules).
Press key to go back to “MAIN MENU”; otherwise the control unit displays the last
configuration panel until it reaches the 15-minute time-out, after which the status screen will
be displayed.
Press twice
6.3
Assignment of the sensors
The configured system alone cannot trigger the alarm mode operations (solenoid valves,
sirens, etc...) if there is an alarm, because the detector alarm commands are not transmitted
to any relay module or display module. Instead, any alarms will always be transmitted to the
relay module of the UCE40... control unit (RM0) that is assigned to all the detectors.
Start from “MAIN MENU”, press until the pointer is positioned over the wording
“SENSOR ASSIGNMENT”, then press to enter the sub-screen.
M A I N M E N U
I N S T A L L A T I O N S T A T E
S E N S O R L I S T
E X P I R E D S E N S O R L I S T
Fig. 6.13 – Fine configurazione
N E W I N S T A L L A T I O N
S 0 4 R M 0 1 D M 0 1 A M 0 1
P R E S S D E V I C E B U T T O N
D M 0 1
Fig. 6.12 – Finestra video dopo aver
configurato quattro sonde, un
modulo relè ed un modulo
display
SENSIGAS
MDD40
T
B
5
T
B
6
E
2
E
1
S1
1 CN1
JP1
ICP
E
4
E
3
P1
Press S1 for display module
configuration