Fig. 4.4 – Position of end-of-line BUS jumpers
4.2
Consumption and sizing of cables
The calculation of the consumption of the various field devices, added to the consumption of
any other 12V powered devices is fundamental to establish how the system needs to be
powered. In particular, if the total of the power as above is less than 30W+/- 1W it is
possible to power the system directly from the control unit if this is fitted with the battery load
and protection circuit (UCE40MPA-CPB order code). For higher powers a UPS
(uninterrupted power supply) unit must be provided. With reference to the main detectors,
the power and the current of each device are shown on the table below:
DEVICE
POWER
[W]
CURRENT
[A]
DEVICE
POWER
[W]
CURRENT
[A]
UCE 40… control
unit
6
0,5
Solenoid valve
12
1
MAR40
2,5
0,208
12V 7Ah battery
7
0,583
MDD40
2
0,166
Visual alarm
2
0,166
MID40
1
0,083
Audible alarm
4
0,333
URG40SS
URG40SE
URG40PS
URG40PE
1,6
0,133
URO40SS
URO40SE
URO40PS
URO40PE
0,7
0,058
URP40SS
URP40SE
URP40PS
URP40PE
1,6
0,133
URB40SS
URB40SE
URB40PS
URB40PE
1,6
0,133
Table 4.2 – Electrical consumption
moduli
(jumper E1,E2)
E1
E
1
Sonde
(jumper E1)
moduli
(jumper E1,E2)
E1
E
1
Sonde
(jumper E1)
Inserita
NON Inserita
E2 E1
E2 E1
E1
NON Inserita
E1
Inserita
moduli
(jumper E1,E2)
E1
E
1
Sonde
(jumper E1)
moduli
(jumper E1,E2)
E1
E
1
Sonde
(jumper E1)
Inserita
NON Inserita
E2 E1
E2 E1
moduli
(jumper E1,E2)
E1
E
1
Sonde
(jumper E1)
moduli
(jumper E1,E2)
E1
E
1
Sonde
(jumper E1)
Inserita
NON Inserita
E2 E1
E2 E1
Inserita
NON Inserita
E2 E1
E2 E1
E1
NON Inserita
E1
NON Inserita
E1
Inserita
E1
Inserita
modules
(jumper E1,E2)
Detectors
(jumper E1)
ON
OFF
ON
OFF
Содержание Sensigas EW40
Страница 2: ...Type N Rev Data Page Total pages EW095 605 5 November 2010 2 96 EsiWelma s r l...
Страница 95: ......