4.4.2
Extended structure
When the devices exceed the power that can be managed by the control unit (30
±
1W)
an external uninterruptible power supply (UPS) is necessary. The example below
represents a system with three boilers, each one fitted with a gas cut-off solenoid valve.
Fig. 4.11 – Extended structure of the system (example)
One methane gas detector (URG40SS) is installed near each boiler and one carbon
monoxide detector (URO40SS) covers the whole premises. A display module is placed at
the entrance to monitor the system status without having to use the control unit.
Each methane gas detector is interfaced with a relay module that powers a local audible
alert in the event of pre-alarm, in alarm threshold one it shuts off the boiler solenoid valve
and in alarm threshold two it shuts off the general gas solenoid valve.