EmoTouch 3 - Installation Instructions
23
Mounting
Fan requirements
Minimal output 5 W
Maximum output 150 W
Voltage 230 V 1N AC
Suitable for use in sauna cabins
Control line connection: 5.2 Connections,
4.2.4 Potential-free contact
A potential-free contact is available on the relay box's circuit board. You
can include this NC contact in any electric circuit to switch an external load
or transmit a signal.
NOTICE
Property damage due to short circuiting
The supply line can short circuit if you use the mains connections
L1, L2 or L3 to supply the electric circuit connected to the poten-
tial-free contact.
Use the EmoTouch 3 mains connections only for the sauna
heater.
Do not connect additional devices to the EmoTouch 3 mains
connections.
Connect the device connected to the potential-free contact
and ensure that it is protected from short circuiting.
Observe the maximum load of the potential-free contact.
Maximum load
Line connection: 5.2 Connections,
Resistive load/alternating current
Max. 250 V AC/10 A
Inductive load/alternating current
500 VA
Direct current
Up to 30 V DC max. 1
0
A (
30
0 W)
Up to 110 V DC max. 0.3 A (33 W)
Up to 220 V DC max. 0.12 A (26.4 W)