STEP NO.
DESCRIPTION
FACTORY SETTING
Slimline 150 Plus
ADJUSTING RANGE
STEP
18
Extract fan mode
switching input 1
5
0 (= Extract fan off)
1 (= Absolute min. flow rate 30 m
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6 (= Maximum flow rate)
7 (= No extract fan activation)
19
Selection input 2
1
0 (= normally open contact)
1 (= 0 - 10V input active)
2 (= normally closed contact)
3 (= input 2/ bypass open
→
12V;
bypass closed
→
0V)
4 (= input 2/ bypass open
→
0V;
bypass closed
→
12V)
20
Minimum voltage input 2
0,0 V
0,0 Volt - 10,0 Volt
0,5 V
21
Maximum voltage input 2
10,0 V
0,0 Volt- 10,0 Volt
0,5 V
22
Conditions
switching input 2
0
0 (off)
1 (on)
2 (= On if conditions bypass open satisfied)
3 (= Bypass control)
4 (= Bedroom valve)
23
Supply fan mode
switching input 2
5
0 (= Input fan off)
1 (= Absolute min. flow rate 30 m
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6 (= Maximum flow rate)
7 (= No input fan activation)
24
Extract fan mode
switching input 2
5
0 (= Extract fan off)
1 (= Absolute min. flow rate 30m
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6 (= Maximum flow rate)
7 (= No extract fan activation)
25
Geo heat exchanger
UIT
OFF (= Valve control geo heat exchanger off)
ON (= Valve control geo heat exchanger on)
26
Minimum temperature geo
heat exchanger (Below this
temperature the valve opens)
5,0 °C
0,0 °C - 10,0 °C
0,5 °C
27
Maximum temperature geo
heat exchanger (Above this
temperature the valve opens)
25,0 °C
15,0 °C - 40,0 °C
0,5 °C